Ol2208 dc digital input module – Nematron Pointe Controller User Manual

Page 254

Advertising
background image

Appendix A: OptiLogic Technical Specifications

Pointe Controller User Guide

252

A.7

OL2208 DC Digital Input Module

The OL2208 DC Digital Input module can be used in either
sourcing or sinking application. (All eight inputs must be
used in the same manner.) Each input is optocoupled to
provide system isolation. Individual LED indicators provide
a visual feedback of current status.

Technical Specifications

Card Cage Power Required

60 mA

Input Type

DC Optocoupled

Inputs

8

Status Indicators

Logic Side LED

Voltage Range

10 – 30 VDC

Input Impedence

2.7K ohms

Min. On Current (per point)

3.3 mA

Max. On Current (per point)

11 mA

Commons

2 (connected internally)

Terminal Strip

Plug In (removable)

Terminal Screws

Slotted (0.1” blade max.)

Max. terminal wire gauge

18 AWG (use copper conductors)

Terminal block torque

2.2 lb-in

Required Temp. rating of
field installed conductors

60°C / 75°C

Weight

1.2 oz (34g)

Type