Appendix A: OptiLogic Technical Specifications

271

o

If Enabled, then Counter Value will be forced to Preset Value

when Input LS becomes ON.

To configure LS Preset, click the

to the right and select an option

(Disabled or Enabled) from the pop-up menu.

Force Preset – Bit to force Counter Value to Preset Value. Whenever the
bit is set to 1, the value is forced. Mapped to an Output Bit tag (%QX).

To configure Force Preset, click the

to the right and select a tag

from the pop-up menu. Each tag can be used only once.

Output tabs

The OL2258 module includes two (2) DC open collector outputs that are
automatically turned on/off according on the current value of the pulse counter.
When the counter value is inside an output’s specified range, the output is turned
on. When the counter value goes outside (above or below) an output’s specified
range, the output is turned off.

Each output is configured separately through its own tab: Output 1 and Output
2
. Both tabs have the same configuration parameters…

Enable Output – Bit to enable and disable the output. When the bit is
set to 1, the output is enabled. When the bit is set to 0, the output is
disabled. Mapped to an Output Bit tag (%QX).

To configure Enable Output, click the

to the right and select a tag

from the pop-up menu. Each tag can be used only once.

Output Status – Bit to which the current status of the output is copied.
(The actual status of the output is automatically controlled by the module
itself.) When the output becomes ON, the bit is set to 1. When the output
becomes OFF, the bit is set to 0. Mapped to an Input Bit tag (%IX).