Appendix A: OptiLogic Technical Specifications

Pointe Controller User Guide

266

Technical Specifications

Card Cage Power Required

400 mA

Inputs (all)

4

Pulse Inputs

2

Status Indicators

Logic Side LED

Counting Modes

Pulse & Direction, Up/Down Count, Quadrature

Count Value

32 Bit Signed

Frequency Data

16 Bit Signed (configurable for 1 sec or 200 msec)

Input Signal Type

Sinking, sourcing, or differential

Input Impedence

2.0K ohms nominal

Input frequency (on pulses)

80/160 KHz maximum

Min. Input On Voltage
(or differential)

4.00V

Min. Input Off Voltage
(or differential)

3.00V

Maximum Input Voltage

28V

Outputs

2

Output Type

Open collector

Commons

1 (connected internally)

Terminal Strip

Plug In (removable)

Terminal Screws

Slotted (0.1” blade max.)

Max. terminal wire gauge

18 AWG (use copper conductors)

Terminal block torque

2.2 lb-in

Required Temp. rating of
field installed conductors

60°C / 75°C

Weight

1.24 oz (35g)