Ol2418 analog current input module – Nematron Pointe Controller User Manual
Page 281

Pointe Controller User Guide
Appendix A: OptiLogic Technical Specifications
279
A.13 OL2418 Analog Current Input
The OL2418 Analog Current Input Module
provides eight (8) amperage sensors. Each
sensor reads the current input amperage,
scales it, and writes the scaled value to a Logic
Memory tag. The value has 14-bit resolution
and is scaled from 0 to 16383 (0x0 to 0x3FFF);
i.e., the minimum amperage is equal to 0, the
maximum amperage is equal to 16383, and all
other amperages are scaled in between.
NOTE: The OL2408 module is currently designed for an amperage range of 4 to 20
mA. This range cannot be changed.
To convert the scaled value back to an actual amperage input, you must
configure a Flow Chart block or Ladder Logic rung to perform the following
calculation:
Amperage Input = [ 16 x ( Scaled Value / 16383 ) ] + 4
Technical Specifications
Card Cage Power Required
700 mA
Inputs
8
Input Type
4-20 mA
Input Impedence
250 Ohms +/- 0.05%
Conversion Type
Successive approximation
Resolution
14 bit (1 in 16384)
Full Scale Calibration Error
+/- 15 counts maximum
+/- 5 counts typical
Offset Calibration Error
+/- 2 counts maximum
Power Isolation
Transformer
Signal Isolation
Optical
Terminal Strip
Plug In (removable)
Terminal Screws
Slotted (0.1” blade max.)
Max. terminal wire gauge
18 AWG (use copper conductors)
Terminal block torque
2.2 lb-in
Required Temp. rating of
field installed conductors
60°C / 75°C
Type
18