Appendix A: OptiLogic Technical Specifications

279

A.13 OL2418 Analog Current Input

The OL2418 Analog Current Input Module
provides eight (8) amperage sensors. Each
sensor reads the current input amperage,
scales it, and writes the scaled value to a Logic
Memory tag. The value has 14-bit resolution
and is scaled from 0 to 16383 (0x0 to 0x3FFF);
i.e., the minimum amperage is equal to 0, the
maximum amperage is equal to 16383, and all
other amperages are scaled in between.

NOTE: The OL2408 module is currently designed for an amperage range of 4 to 20
mA. This range cannot be changed.

To convert the scaled value back to an actual amperage input, you must
configure a Flow Chart block or Ladder Logic rung to perform the following
calculation:

Amperage Input = [ 16 x ( Scaled Value / 16383 ) ] + 4

Technical Specifications

Card Cage Power Required

700 mA

Inputs

8

Input Type

4-20 mA

Input Impedence

250 Ohms +/- 0.05%

Conversion Type

Successive approximation

Resolution

14 bit (1 in 16384)

Full Scale Calibration Error

+/- 15 counts maximum

+/- 5 counts typical

Offset Calibration Error

+/- 2 counts maximum

Power Isolation

Transformer

Signal Isolation

Optical

Terminal Strip

Plug In (removable)

Terminal Screws

Slotted (0.1” blade max.)

Max. terminal wire gauge

18 AWG (use copper conductors)

Terminal block torque

2.2 lb-in

Required Temp. rating of
field installed conductors

60°C / 75°C