Nematron Pointe Controller User Manual

Page 367

Advertising
background image

Pointe Controller User Guide

Appendix C: Ladder Diagram Block Reference

365

Once the block is inserted, you can double-click on it to

configure

it.

Functional Description

This block always passes the Enable input state (EN) through to the Enable Out
output state (ENO) without change; when EN becomes on, ENO is turned on, and
when EN becomes off, ENO is turned off.

When EN becomes on, the block function is executed: the square root of the
Input Value (IN) is calculated and the result is placed in the Output Value (OUT).

The block function is executed every time the ladder is

scanned

, so long as EN

remains on. If EN becomes off, then OUT remains at its last calculated value until
EN becomes on and the block function is executed again.

Configuration Reference

The parameters of this block are described in the following table:

Param

Name

Config

Var Type

Description

EN

Enable

no

-

The state of the rung (off/on)
received from the left.

ENO

Enable
Out

no

-

The state of the rung (off/on)
passed to the right.

IN

Input
Value

req

real only*

Numeric

The input value. If a Numeric value
is manually entered, it must be real
/ floating.

OUT

Output
Value

req

real only*

The result of calculating the square

root of the input value.

* Any 32-bit Real (F) Input, Output, or Memory tag. For more information, see “

Defining Input,

Output, Memory tags

” on page 114

.

NOTE: This function cannot calculate the square root of a negative input value. If
the input value is negative, the value “1.#IND00” (indefinite) is placed in the
output. No error is generated.

Advertising