Warning, Important – Mammoth V-Cube User Manual

Page 20

Advertising
background image

6. Fan, wheels, housings and drive assemblies 6. should

be checked for dirt buildup annually and cleaned
if necessary to keep them from becoming unbal-
anced and to prevent loss of airflow. Clean with
compressed air to reduce any dirt, dust, lint or larger
particulates that have bonded to the fan impeller
housing or drive assembly. Block dirt from entering
the unit and ductwork if necessary or remove fan
assembly from unit. Alternatively use low pressure
steam, a degreaser and rag. If a sheave requires
cleaning, detergent and water can also be used. En-
sure the belt is dry before starting up the unit.

!

WARNING

Many of the following steps need to be performed with
the unit powered off and locked out. Disconnect the
main power switch to the unit before performing service
and maintenance procedures.

Table 4: Recommended Grease Quantity

Shaft Size

Maximum Grease Capacity

of Bearing Chamber

Inches

Millimeters

Ounces

Kilograms

0.500–0.750

13–19

0.125

0.004

0.875–1.187

25–31

0.375

0.011

1.250–1.500

32–38

0.625

0.018

1.687–1.937

43–49

0.875

0.025

2.000–2.437

51–62

1.250

0.035

2.500–2.937

63–75

2.000

0.056

3.000–3.437

76–87

3.500

0.098

3.500–4.000

89–102

6.000

0.168

4.187–4.937

106–125

10.000

0.280

Table 5: Generally Recommended Relubrication Frequency in Months

Operating

Speed (RPM)

0.500–1.000”

[13–35 mm]

1.125–1.500”

[28–38 mm]

1.625–1.937”

[41–49 mm]

2.000–2.500”

[50–63 mm]

2.687–3.187”

[68–81 mm]

3.437–3.937”
[87–100 mm]

up to 500

6

6

6

6

5

4

500–1,000

6

6

6

5

4

3

1,000–1,500

5

5

5

4

3

3

1,500–2,000

5

4

4

3

2

1

2,000–2,500

4

4

3

2

1

2,500–3,000

4

3

2

1

2

3,000–3,500

3

2

2

2

3,500–4,000

3

2

1

4,000–4,500

2

1

1

4,500–5,000

2

1

IMPORTANT

Be careful not to remove or dislodge balancing clips on
the fan blades while cleaning.

VCES-V-CUBE-IOM-1A

20