Mammoth V-Cube User Manual
Page 43
3 – Operating Electric Coil Heaters
3.1.–.Minimum.Airflow
Ensure that sufficient airflow as marked on the nameplate
is passing through the heater. Airflow should be evenly
distributed across the entire face of the heater. Use air
turning vane at duct elbows and splitter damper at duct
branchoffs to streamline the airflow in the heater. Use
suitable airflow sensing device or interlock the heater with
fan. An insufficient airflow will lead to the opening of the
autoreset thermal cut-out or damage to the heating ele-
ments.
3.2.–.Warning
The air flowing through the duct where the heater is in-
stalled shall not contain any combustible particles, nor any
flammable vapor or gas.
3.3.–.Air.Temperature
The air temperature should not exceed 120ºF [49ºC] at the
heater outlet.
3.4.–.Minimum.Static.Pressure.and.Air.Direction
The heater is protected by a differential pressure switch.
To keep the contact of this switch closed, it is necessary to
maintain a minimum total pressure of 0.07” of water for a
constant flow.
3.5.–.Manual.Reset.Thermal.Cut-out
This protection device is standard on all heaters of less
than 300 volt and 30 kW and is optional on all other heat-
ers. Please check the auto-reset thermal cut-out before
resetting the manual thermal cut-out. If any defect has
been detected in the auto-reset thermal cut-out, it will be
necessary to replace it before resetting the manual reset
thermal cut-out.
4 – Maintenance
All electric coil heaters have been designed to operate
long term without problems. Those responsible for equip-
ment and maintenance should be aware of the following
suggestions.
4.1.–.Visual.Inspection
It is strongly recommended to complete a periodic inspec-
tion. This precautionary step will help to keep your instal-
lations operating well. Note these eventual first signs of
problems:
• Accumulation of dust on the heating elements.
• Signs of overheating on the heater frame.
• Traces of water or rust on the control box.
4.2.–.Electrical.Inspection
Two weeks after start-up, all electric connections to con-
tactors should be checked and tightened up. Before each
heating season, check the resistance between the heating
elements and ground. It is also recommended to check
the electrical connections to heating elements, magnetic
contactors and main power lugs. This inspection is recom-
mended monthly during the first four months of opera-
tion. After that, two inspections per heating season are
sufficient.
4.3.–.Checkpoints
• Check all fuses.
• Check the resistance to ground for each circuit.
• Check the resistance phase-to-phase for each circuit.
• Check the tightening of connections at all contactors
and heating elements.
• Check all contactors.
4.4.–.Off-season.Maintenance
Where tubular heating elements are used, it is strongly
recommended that you start the heating system from time
to time. This precaution will prevent moisture from perco-
lating through the terminal gaskets into the heating ele-
ment and accumulating in the insulating powder. Should
a heater be shut off for a long period, we recommend
that you check carefully the resistance to ground for each
circuit. It is important not to power a heater when too low
a resistance to ground has been measured. It is also rec-
ommended to pay attention to any other heater operating
in normal conditions. Control components such as step
controllers or modulating valves (SCR) should be main-
tained and checked according to respective manufacturers
instructions. Any defective components should be replaced
only with identical original parts.
VCES-V-CUBE-IOM-1A
43