Serial Number: _____________________________________

Table C7: Start-up Readings – Water Source Heat Pump (WSHP)/Water Cooled Condenser (WCC)

Waterside Cooling Mode

Waterside Heating Mode

Entering

Temperature

(°F/°C)

Leaving

Temperature

(°F/°C)

Temperature

Difference

(°F/°C)

Entering

Temperature

(°F/°C)

Leaving

Temperature

(°F/°C)

Temperature

Difference

(°F/°C)

Entering

Pressure

(PSI)

Leaving

Pressure

(PSI)

US GPM

Condenser 1
Condenser 2
Condenser 3
Condenser 4
Condenser 5
Condenser 6
Condenser 7
Condenser 8
Condenser 9
Condenser 10
Condenser 11
Condenser 12
Condenser 13
Condenser 14
Condenser 15
Condenser 16

Table C8: Start-up Readings – Electric Heating Coil

Stage

L1 Amps

L2 Amps

L3 Amps

Check for Hot Pots

1
2
3
4
5
6

Item

Description

Yes

No

1

Is the unit stored indoors in a clean, dry environment?
Is the indoor storage facility temperature regulated to within 50ºF to 75ºF?
Is the indoor storage facility humidity regulated to within 10% to 50% RH?

2

Is the unit mounted on a level surface along the perimeter of the base with weight evenly
distributed?

3

Has the plastic wrapping been removed from the unit to perform inspection and mainte-
nance?
Has the plastic wrapping been saved for future use?
Has the plastic wrapping been re-applied to the unit when the unit has been shipped to
jobsite?

Recommend Has a desiccant pouch been placed in the control panel?

VCES-V-CUBE-IOM-1A