FANWALL

®

.Array

Maintenance Schedule

FANWALL array of multiple direct driven plenum fan and
motor “cubes” are equipped with permanently sealed
bearings and do not require lubrication. The following
maintenance schedule is recommended.

1. Monthly

a. Check the fan wheel to inlet cone alignment for

possible noise from the wheel rubbing against
the inlet cone. See Fan Wheel/Cone Alignment
below for instructions.

2. Every six months

a. Check motor bearings for possible binding noise

or overheating.

b. Check fan wheels for dirt and grease accumula-

tion. Clean as necessary. Do not use any caustic
cleaning solutions.

3. Annually

a. Lightly lubricate damper and linkage bushings on

backdraft dampers (if equipped).

4. Every two years

a. Examine fan housings and motor pedestal for

corrosion. Clean and touch up with paint as nec-
essary.

Fan Wheel and Motor Removal

1. Disconnect power to the fan array control panel

before maintenance. Follow all lockout and tag out
procedures.

2. Remove the optional safety screen (if provided) on

the motor end only of the cube in question by re-
moving all four hex screws from the holding flange
that retains the safety screen (see Figure 16).

3. Disconnect the four-wire electrical cable from the

motor junction box. Make note of wire locations for
reinstallation later (see Figure 17).

4. Mark motor pedestal location on the motor pedestal

mounting angles (both sides), then loosen and re-
move (four) ½” bolts that retain the motor pedestal
to the mounting angles (see Figure 18).

!

WARNING

Many of the following steps need to be performed with
the unit powered off and locked out. Disconnect the
main power switch to the unit before performing service
and maintenance procedures.

Figure 15: FANWALL array

Figure 16: Remove safety screen on motor end

Figure 17: Remove electrical cable

Figure 18: Remove motor pedestal retaining bolts

VCES-V-CUBE-IOM-1A