Appendix G: V-Cube™ Maintenance Summary Chart

Table G1: Maintenance Summary Chart – V-Cube

Item

No. Description

Monthly

Quarterly

Semi-

annually

Annually

General

1

Inspect the general condition of the unit.

x

2

Remove any dirt or debris.

x

3

Check for unusual noise or vibration.

x

4

Lubricate the door latch mechanisms.

x

Fans

5

Clean fans with stream of water.

x

6

Align or replace belts and drives.

x

7

Adjust belt tension.

x

8

Check motor voltage and current.

x

9

Lubricate the motor and shaft bearings.

x

10 Lubricate motor base adjusting screws.

x

Dampers

11 Visual inspection for dirt or leakage.

x

12 Lubricate damper linkage.

x

Air filters

13 Clean and replace prefilters.

x

14 Clean and replace final filters.

x

15 Inspect holding frames/sliding rack.

x

Coils

16 Clean the coils.

x

17 Winterize the water coil.

x

Electric

34 Verify all electrical connections; tighten if necessary.

x

35 Verify all fuse holders.

x

36 Verify all motor overload settings.

x

Condenser
fans

37 Inspect fan blades for cracks.

x

38 Inspect for wear and tension.

x

Cooling
section

39

Look for oil on all refrigeration components (including coils,
compressors, etc.) to indicate a refrigerant leak.

x

40 Verify for proper superheat.

x

41

Verify each circuit refrigerant site glass when the circuit is
operating under steady state, full load conditions. It should be full
and clear. If not, look for refrigerant leaks.

x

VCES-V-CUBE-IOM-1A

45