Appendix E: Electric Heating Coil and Controls Information

This electric heating coil module covered by this appen-
dix is a component of a “Listed” product, subject to the
guidelines of application as designated by the Certifying
Agency and outlined in the appliance Manufacturer’s In-
stallation and Operation Instructions.

The information provided in this appendix applies to the
electric heating coil module, installed in the appliance and
to its operation, maintenance and service. Refer to the ap-
pliance manufacturer’s instructions for information related
to all other components.

1 – Mechanical Installation of Electric Coil

Heaters

1.1 – Handling

1.1.1 Remove the shipping covers just before installation.
1.1.2 Inspect the heater carefully and report any dam-

age to the manufacturer.

Do not install a damaged heater.

1.2 – Installation

Heater.Position

1.2.1 The axis of the duct must always be perpendicular

to the face of the heater.

1.2.2 The heating elements must always be installed

horizontally.

Model SC or ST (Slip-in Type)

1.2.3 Cut an opening in the side of the duct.
1.2.4 Slip the heater into the duct until the hole is com-

pletely covered by flanges around the heater.

1.2.5 Fasten the heater to the duct with sheet metal

screws and seal openings with a suitable sealing
compound.

1.2.6 If the heater is heavy, use additional hangers to

support the heater.

Model FC or FT (Flanged Type)

1.2.7 Flange both ends of the duct outwards on three

sides to match the heater’s flanges.

1.2.8 Fasten the heater to the duct with sheet metal

screws (for heavy heaters, use nuts and bolts and
additional hangers to support the heater).

1.2.9 Seal openings with a suitable sealing compound.

2 – Electrical Installation of Electric Coil

Heaters

2.1.Disconnect.all.power.sources.before.opening.

the.control.box.and.working.within.
2.2.Read.the.nameplate.carefully.and.consult.

wiring.diagram.before.starting.to.wire.
2.3.–.Supply.Wires

Use only wires suitable for 167ºF [75ºC]. Wires shall be
sized according to the Canadian Electrical Code require-
ments. All wires must be brought in through knock-outs.

2.4.–.Disconnecting.Means

Install a disconnect switch close to the heater according
to the code unless a disconnect switch is already built into
the heater.

2.5.–.Control.Circuit.Wiring

Use Class II wiring for control circuit connections to the
duct heater.

2.6.–.Magnetic.Contactors

If magnetic contactors are mounted outside of the duct
heater, use only contactors approved for:

• 250,000 operations when controlled by auto-reset

thermal cut-out (A) and by other switching devices in
series with this cut-out (thermostat, step controller,
airflow switch, etc.).

• 100,000 operations when controlled by auto-reset

thermal cut-out (A) alone.

• 100,000 operations when controlled by auto-reset

thermal cut-out (A) plus manual reset cut-out in se-
ries (A and M).

• 6,000 operations when controlled by manual reset

cutout (M) alone.

2.7.–.External.Controls.Ratings

Rating of external control devices shall be suitable for han-
dling the VA ratings as marked on the nameplate; other-
wise, a backup relay must be used.

2.8.–.Airflow.Interlock

Heaters are generally supplied with one extra terminal
marked for fan interlock or air sensing device connection.
Remove jumper between terminals I and C before con-
necting the fan interlock. Select a suitable airflow sensing
device of the differential pressure sensing type, with snap
acting contacts. A slow make, slow brake device may
cause undue cycling and in some instances chattering of
the contactors. When fresh air dampers are used, make
sure the heater is properly interlocked to prevent it from
being energized before the damper is fully open.

IMPORTANT

• Do not install spray humidifiers upstream of duct.

Install it downstream instead.

• Do not cover the control box with thermal insulat-

ing materials.

• Use special air intake louvers of weatherproof con-

struction for preheat duct heaters to avoid intake of
water or snow particles.

• Make sure that motorized damper blades are not

blocked with snow or dirt. Inspect the dampers
regularly to ensure a suitable airflow.

VCES-V-CUBE-IOM-1A