BEFORE INSTALLATION

T775A/B/M SERIES 2000 CONTROLLER

3

62-0254–03

BEFORE INSTALLATION

Review the “Specifications” on page 35 before
installing the controller.

When Installing This Product

1.

Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.

2.

Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for your appli-
cation.

3.

Installer must be a trained, experienced service
technician.

4.

After installation is complete, check out product
operation as provided in these instructions.

INSTALLATION AND SETUP

The following installation procedures are typically
performed in the order listed:

1.

Mounting — see “Mounting” below.

2.

Wiring — see “Wiring” on this page.

3.

Checkout — see page 10.

4.

Programming — see page 13.

5.

Scheduling (optional) — see page 30.

Additional topics are:

Temperature sensor calibration begins on page 10.

Interface overview begins on page 11.

Setup (for advanced options) begins on page 17.

Summary menu begins on page 34.

Troubleshooting begins on page 34.

MOUNTING

This section describes the mounting procedures for the
controller and temperature sensor(s).

Controller Mounting

IMPORTANT

Avoid mounting in areas where acid fumes or
other deteriorating vapors can attack the metal
parts of the controller circuit board, or in areas
where escaping gas or other explosive vapors
are present.

IMPORTANT

The controller must be mounted in a position that
allows clearance for wiring, servicing, and
removal.

Use a screwdriver to pry out only the knockouts that you
will use.

If mounting on DIN rail, be sure to remove the knockouts
before mounting. See “Controller Wiring” on page 5 and
Fig. 7 on page 6 for recommended knockout usage and
locations. If you do not use an opened knockout be sure
to cover it.

Mount the controller on any convenient interior location
using the four mounting holes provided on the back of the
enclosure using #6 or #8 screws (screws are not provided
and must be obtained separately). Use controller
dimensions in Fig. 1 on page 2 as a guide.

The controller may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1
permits proper viewing of the LCD display and use of the
keypad.

NEMA 4 Enclosure Mounting

For models with NEMA 4 enclosures, ensure that
waterproof wire/conduit fittings are used at the knockouts
for all wiring attachments. See Fig. 7 on page 6 for
knockout locations.

IMPORTANT

For NEMA 4 enclosures, be sure to cover and
seal all unused open knockouts.

Temperature Sensor(s) Mounting and
Location

Temperature sensors may be located up to 1,000 feet
(304 m) from the T775A/B/M controller. See Table 3 on
page 10 for calibration guidelines.

The sensors may be mounted on a wall or panel for
sensing space temperature, strapped to a pipe or inserted
in an immersion well (see Fig. 2) for hot or cold water
sensing, or taped to a standard cap or bulb holder for duct
air sensing. To prevent moisture or condensation entering
the sensor through the lead wire holes, mount the sensor
with the lead wires exiting the bottom of the sensor.

NOTES:

1.

The included sensor is not designed for very
wet applications. For immersion applications,
an immersion well is used.

2.

Heat conductive compound must be used in
immersion wells.

3.

See “Temperature Sensors” on page 2 for this
type of installation.

Fig. 2. Sensor inserted in immersion well.

NOTE:

Multiple sensors may be parallel-series wired to
sense average temperatures in large spaces.
See Fig. 3 on page 4.

WIRING

All wiring must comply with applicable electrical codes
and ordinances, or as specified on installation wiring
diagrams. Controller wiring is terminated to the screw
terminal blocks located inside the device.

The remainder of this section describes the temperature
sensor wiring and the T775A/B/M controller wiring.

SENSOR

PLACED

IN WELL

IMMERSION

WELL

1/2 NPT

USE HEAT

CONDUCTIVE

COMPOUND

M24470