T775A/B/M SERIES 2000 CONTROLLER

2. SETUP (ADVANCED OPTIONS)

62-0254–03

22

Fig. 47. Setup - Outputs - Mod Out - Type.

2.3.1.1. TYPE

(of output signal)

1.

From the Mod menu, use the

S and T buttons to

highlight TYPE.

2.

Press the

X button to display the Type selections.

3.

Use the

Sand T buttons to highlight the desired

output type.

Default: 4-20 mA

4.

Press the

X button to accept the selected type and

return to the Mod menu.

Fig. 48. Setup - Outputs - Mod Out - Minimum Output

Percentage.

2.3.1.2. MIN OUT %

The minimum output % prevents the output from dropping
below the value entered. This value can be useful to
maintain minimum damper position.

Using the time clock or digital input to disable the output
forces the output to 0%.

1.

From the Mod menu, use the

S and T buttons to

highlight MIN OUT %.

2.

Press the

X button to display the Min Out %.

3.

Use the

S and T buttons to increase/decrease the

desired value from 0% to 100% in 1% increments.

Default: 0%
Range: 0 to 100%

4.

Press the

X button to accept the percentage and

return to the Mod menu.

Fig. 49. Setup - Outputs - Mod Out - Integral.

2.3.1.3. INTEGRAL

1.

From the Mod menu, use the

S and T buttons to

highlight INTEGRAL.

2.

Press the

X button to display the Integral seconds.

3.

Use the

S and T buttons to increase/decrease the

value from 0 to 3,600 in 10 second increments.

Default: 400 seconds
Range: 0 to 3,600 seconds

4.

Press the

X button to accept the seconds and

return to the Mod menu.

NOTES:

1. The Integral time is factory set for 400 seconds. This

is a good middle range and should satisfy many
applications. The integral time can be increased for
applications where sensed response is slow, and can
be decreased for applications where sensed
response is fast (e.g. discharge air control).

2. As a starting point, an optimal integral time for

discharge air typically ranges from 12 to 200
seconds. An optimal integral time for room control
typically ranges from 60 to 2,500 seconds. The
purpose of integral action is to reduce or eliminate
the offset from setpoint during steady state control
that is often seen in proportional only control.

3. Keep in mind that control is most sensitive to

throttling range. Adjust the throttling range first
before any adjustment to integral time. Adjust
throttling range to be as wide as possible to start
since this will provide the most stable control.
Remember that the integral will eliminate the steady
state error so you do not need to have a small
throttling range to have accurate control. (Integral
action allows for controlling to a setpoint even with a
wide throttling range).

SETUP
OUTPUTS
MOD

1

TYPE

SETUP

OUTPUTS

MOD 1

TYPE

SELECT

TYPE FOR

MOD 1

4 - 20 mA

0-10 V

2-10 V

SERIES 90

M24513

SETUP

OUTPUTS

MOD 1

MIN OUT %

ENTER

MINIMUM

PERCENT FOR

MOD 1

SETUP

OUTPUTS

MOD 1

MIN OUT %

0

%

M24514

SETUP

OUTPUTS

MOD 1

INTEGRAL

ENTER

INTEGRAL

TIME FOR

MOD 1

SETUP

OUTPUTS

MOD 1

INTEGRAL

400

SEC

M24515

Advertising