T775A/B/M SERIES 2000 CONTROLLER

2. SETUP (ADVANCED OPTIONS)

62-0254–03

18

Fig. 36. Setup - Sensors - Sensor A Menu.

2.2.2. SENSOR A

1.

From the Sensors menu, highlight SENSOR A.

2.

Press the

X button to display the Sensor A selec-

tions.

Fig. 37. Setup - Sensors - Sensor A - Units.

2.2.2.1. UNITS

(°F or °C)

IMPORTANT

This is a global change and affects the unit
values for all temperature parameters on all
displays.

The UNITS screen displays only for Sensor A.

1.

From the Sensor A selections, use the

S and T

buttons to highlight UNITS.

2.

Press the

X button to display the temperature units.

3.

Use the

S and T buttons to highlight F or C.

Default: F (Fahrenheit)

4.

Press the

X button to accept the units and return to

the Sensor A selections.

Fig. 38. Setup - Sensors - Sensor A - Calibrate.

2.2.2.2. CALIBRATE

(the sensor)

Ensure that the wire size calibration value is within the
limits. See “Temperature Sensor Calibration” on page 10.

1.

From the Sensor A selections, use the

S and T

buttons to highlight CALIBRATE.

2.

Press the

X button to display the calibration degree

value.

3.

Use the

S and T buttons to increase/decrease the

desired calibration degrees.

Default: 0.0
Range: +/-10°F (+/-6°C)

4.

Press the

X button to accept the value and return to

the Sensor A selections.

Fig. 39. Setup - Sensors - Sensor A - Label.

2.2.2.3. LABEL

(the sensor input)

For a sensor already labeled, the display positions to and
highlights that label.

1.

From the Sensor A selections, use the

S and T

buttons to highlight LABEL.

2.

Press the

X button to display the label list.

3.

Use the

S and T buttons to scroll through list and

highlight the desired label.
You may need to scroll up or down to view all possi-
ble labels.

4.

Use the

X button to accept the highlighted label

and exit the list.

NOTE:

The label names in list order are: Sensor, Boiler,
Outdoor, Duct, Dischrg, Chiller, Room, Supply,
Return, and Animals.

SETUP
SENSORS

SENSOR A

SETUP

SENSORS

SENSOR A

UNITS

CALIBRATE

LABEL

EXIT

M24502

SETUP
SENSORS

SENSOR

A

UNITS

SETUP

SENSORS

SENSOR A

UNITS

SELECT

UNITS FOR

SENSOR A

DEG F

DEG C

M24503

SETUP

SENSORS

SENSOR

A

CALIBRATE

ENTER

VALUE TO

CALIBRATE

SENSOR A

SETUP

SENSORS

SENSOR A

CALIBRATE

M24504

0.0

F

o

SETUP
SENSORS
SENSOR

A

LABEL

SETUP

SENSORS

SENSOR A

LABEL

SELECT

LABEL FOR

SENSOR A

SENSOR A

BOILER A

OUTDOOR A

DUCT A

DISCHRG A

CHILLER A

ROOM A

M24505