T775A/B/M SERIES 2000 CONTROLLER

2. SETUP (ADVANCED OPTIONS)

62-0254–03

20

Fig. 42. Setup - Sensors - Sensor B - Limit.

2.2.4. LIMIT

(Sensor B only)

For the T775M2030 and T775M2048 models only, the
LIMIT item displays on the Sensor B menu.

NOTE:

The LIMIT option acts only on Modulating
Output 1.

1.

From the Sensors menu, use the

T button to high-

light SENSOR B.

2.

Press the

X button to display the Sensor B menu.

3.

Use the

S and T buttons to select the LIMIT item.

4.

Use the

X button to display the Limit selections.

5.

Use the

S and T buttons to select the desired limit,

(Disable, Hi Limit, or Low Limit).

Default: Disable

6.

Press the

X button to accept the value and return to

the Sensor B menu.

When you select Hi Limit or Low Limit, the Sensor B menu
changes and adds the Hi/Low Limit and Throttling Range
items.

If you are setting a Hi or Low Limit, continue with “2.2.4.1.
HI LIMIT or LOW LIMIT (Sensor B only)”.

If you selected Disable for the Limit value, continue with
“2.3. Setting up the Outputs” on page 21.

Fig. 43. Setup - Sensors - Sensor B - Hi/Low Limit

(showing Hi Limit).

2.2.4.1. HI LIMIT or LOW LIMIT

(Sensor B only)

Fig. 43 shows the Hi Limit (Heat mode), but the process is
the same for setting the Low Limit (Cool mode). For
proper operation, the high limit should be used only in the
Heat mode, and the low limit only in the Cool mode.

Sensor B can be assigned a high/low limit, so that as you
are controlling temperature at Sensor A, the control
adjusts its modulating output to prevent exceeding the
user-entered limit for Sensor B.

1.

From the Sensor B menu, use the

T button to high-

light HI LIMIT or LOW LIMIT.

2.

Press the

X button display the LIMIT value.

3.

Use the

S and T buttons to increase/decrease the

desired Limit value.

4.

Press the

X button to accept the value and return to

the Limit menu.

SETUP

SENSORS

SENSOR B

LIMIT

SETUP

SENSORS

SENSOR B

LIMIT

SELECT

HI/LOW

LIMIT FOR

SENSOR B

DISABLE

HI LIMIT

LOW LIMIT

M24508

SETUP

SENSORS

SENSOR B

UNITS

CALIBRATE

LABEL

LIMIT

HI LIMIT

THROT RNG

EXIT

SETUP

SENSORS

SENSOR B

ENTER

VALUE FOR

SENSOR B

HI LIMIT

SETUP

SENSORS

SENSOR B

HI LIM

90

F

o

M24509