Exit options setup, Setting up the relays, Type – Van Air Systems FP-3 Kit User Manual

Page 34

Advertising
background image

T775A/B/M SERIES 2000 CONTROLLER

2. SETUP (ADVANCED OPTIONS)

62-0254–03

26

Fig. 59. Setup - Outputs - Options - Exit.

2.3.3.5. Exit Options Setup

Press the

W button (or highlight EXIT and press the X

button) to exit and return to the Outputs menu.

Continue with “2.3.4. Setting up the Relays”

Fig. 60. Setup - Outputs - Relay Menu.

2.3.4. Setting up the Relays

1.

From the Outputs menu, use the

S and T buttons

to highlight the desired relay (1-4 depending on
model).

2.

Press the

X button to display the selected relay

menu.

The TYPE selection shown in Fig. 60 displays only for
Relay 1 and Relay 3.

Continue with the remainder of section 3.4 to setup the
relay outputs.

Fig. 61. Setup - Outputs - Relay - Type.

2.3.4.1. TYPE

(standard or floating)

The Floating option is only available on the T775B2016,
T775B2024, T775B2032, and T775B2040 models.

For these models, this selection displays only for Relay 1
and/or Relay 3.

1.

Press the

X button to display the Type values.

2.

Use the

S and T buttons to select STANDARD OR

FLOATING.

Default: STANDARD (not floating)

3.

Press the

X button to accept the value and return to

the Relay menu.

If you select FLOATING, the relays are paired (1-2 or 3-4)
and are setup together. Continue with “2.3.4.1.1. Floating
Relay Menu”.

If you select STANDARD, go to “2.3.4.2. SCHEDULE” on
page 28.

SETUP

OUTPUTS

OPTIONS

USE SCHED

MIN OFF

DI OPTION

SHOW RT

EXIT

M24525

SETUP

OUTPUTS

RELAY

1

SETUP

OUTPUTS

RELAY 1

TYPE

SCHEDULE

RESET

RESET RT

EXIT

M24526

SETUP

OUTPUTS

RELAY 1

TYPE

SETUP

OUTPUTS

RELAY 1

TYPE

SELECT

TYPE FOR

RELAY 1

STANDARD

FLOATING

M24527