T775A/B/M SERIES 2000 CONTROLLER

2. SETUP (ADVANCED OPTIONS)

62-0254–03

28

Fig. 65. Setup - Outputs - Floating Relay - Derivative.

2.3.4.1.1.3. DERIVATIVE

(modulating/floating relay only)

The Derivative option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.

1.

From the menu, use the

S and T buttons to high-

light DERIVATIV.

2.

Press the

X button to display the actuator value.

3.

Use the

S and T buttons to increase/decrease the

desired number of seconds.

Default: 0 seconds
Range: 0 to 3,600 seconds)

4.

Press the

X button to accept the value and display

the SCHEDULE option.

Continue with “2.3.4.2. SCHEDULE” for the remaining
relay selections.

Fig. 66. Setup - Outputs - Relay - Schedule.

2.3.4.2. SCHEDULE

This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (see page 24).
When selected, individual outputs default to follow the
schedule.

1.

Press the

X button to display the Schedule values.

2.

Use the

S and T buttons to select YES or NO.

Default: YES

3.

Press the

X button to accept the value and return to

the Relay menu.

An individual output can be selected to be controlled or
not controlled by the schedule.

If NO is selected, the Setback selection does not appear
in the Program menu for this output.

Fig. 67. Setup - Outputs - Relay - Reset Runtime.

2.3.4.3. RESET RT

(run time hours)

This selection displays only if “Show RT = YES” is
selected during Output Options setup (see page 25).

1.

From the Relay menu, press the

X button to display

the Reset RT values.

2.

Use the

S and T buttons to select YES or NO.

Default: NO

3.

Press the

X button to accept the value and return to

the Relay menu.

Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.

NOTE:

Run times can be reset to zero for each individ-
ual relay. You must do this for each relay that
you want to reset to zero.

SETUP

OUTPUTS

FLOAT 1

DERIVATIV

ENTER

DERIVATIVE

TIME FOR

FLOAT 1

SETUP

OUTPUTS

FLOAT 1

DERIVATIV

0

SEC

M24531

SETUP
OUTPUTS

RELAY 1

SCHEDULE

SETUP

OUTPUTS

RELAY 1

SCHEDULE

USE

SCHEDULE

FOR

OUTPUTS

YES

NO

M24532

SETUP

OUTPUTS

RELAY 1

RESET RT

SETUP

OUTPUTS

RELAY 1

RESET RT

RESET

RUN TIME

FOR

RELAY 1

YES

NO

M24533