2. SETUP (ADVANCED OPTIONS)

T775A/B/M SERIES 2000 CONTROLLER

27

62-0254–03

Fig. 62. Setup - Outputs - Floating Relay - Menu.

2.3.4.1.1. Floating Relay Menu

The Floating option is only available on the T775B2016,
T775B2024, T775B2032, and T775B2040 models.

When Relay 1 or Relay 3 is setup as floating, relays are
paired and the Float 1 or Float 2 menu displays with the
selections shown in Fig. 62.

Fig. 63. Setup - Outputs - Floating Relay - Actuator.

2.3.4.1.1.1. ACTUATOR

(floating relay only)

The Actuator option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.

1.

From the menu, use the

S and T buttons to high-

light ACTUATOR.

2.

Press the

X button to display the actuator value.

3.

Use the

S and T buttons to increase/decrease the

desired number of seconds.

Default: 90 seconds
Range: 0 to 3,600 seconds)

4.

Press the

X button to accept the value and display

the INTEGRAL option.

The actuator run time is defined as the time needed to
move the actuator from the fully closed to fully open
position and visa versa.

Fig. 64. Setup - Outputs - Floating Relay - Integral.

2.3.4.1.1.2. INTEGRAL (

modulating/floating relay only)

The Actuator option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.

1.

From the menu, use the

S and T buttons to high-

light INTEGRAL.

2.

Press the

X button to display the actuator value.

3.

Use the

S and T buttons to increase/decrease the

desired number of seconds.

Default: 400 seconds
Range: 0 to 3,600 seconds)

4.

Press the

X button to accept the value and display

the DERIVATIV option.

See Integral NOTES on page 22 for additional information
about setting the Integral time.

SETUP

OUTPUTS

FLOAT

1

SETUP

OUTPUTS

FLOAT 1

TYPE

ACTUATOR

INTEGRAL

DERIVATIV

SCHEDULE

RESET

EXIT

M24528

SETUP

OUTPUTS

FLOAT 1

ACTUATOR

ENTER

ACTUATOR

TIMING FOR

FLOAT 1

SETUP

OUTPUTS

FLOAT 1

ACTUATOR

90

SEC

M24529

SETUP

OUTPUTS

FLOAT 1

INTEGRAL

ENTER

INTEGRAL

TIME FOR

FLOAT 1

SETUP

OUTPUTS

FLOAT 1

INTEGRAL

400

SEC

M24530