MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Power Supply Calculations

Calculating the System Current Draw

Table 5.3 contains three columns for calculating current draws. For maximum output current avail-
able per circuit and per panel, refer to Section 1.2, “Specifications”, on page 14
. For each column,
calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the
totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 111.

Device Type

Calculation Column 1

Primary, Non-Fire Alarm Current

(amps)

Calculation Column 2

Secondary, Fire Alarm Current

(amps)

Calculation Column 3

Secondary, Non-Fire Alarm Current

(amps)

Qty

X[current draw]= Total

Qty

X [current draw] = Total

Qty

X[current draw]=

Total

Main Circuit Board

1

X[0.095]=

0.095

1

X[0.221]

1, 2

=

0.221

1

X[0.095]=

0.095

CAC-5X

[ ]

X[0.001]=

[ ]

X[0.001]=

[ ]

X[0.001]=

4XTMF

[ ]

(1 max.)

X[0.005]=

[ ]

X[0.011]1=

[ ]

X[0.005]=

ANN-SEC Card

[ ]

(1 max.)

X[0.003]=

[ ]

(1 max.)

X[0.003]=

[ ]

(1 max.)

X[0.003]=

ANN-80(C)

[ ]

X[0.037]=

[ ]

X[0.040]=

[ ]

X[0.015]=

ANN-I/O

[ ]

X[0.035]=

[ ]

X[0.200]=

[ ]

X[0.035]=

ANN-RLY

[ ]

X[0.015]=

[ ]

X[0.075]=

[ ]

X[0.015]=

ANN-(R)LED

[ ]

X[0.028]=

[ ]

X[0.068]=

[ ]

X[0.028]=

ANN-S/PG

[ ]

X[0.045]=

[ ]

X[0.045]=

[ ]

X[0.045]=

2-wire Detector

Heads

[ ]

X[ ]

3

=

[ ]

4

X[0.040]=

[ ]

X[ ]3=

4-wire Detector

Heads

[ ]

X[ ]3=

[ ]4

X[0.040]=

[ ]

X[ ]3=

Power Supervision

Relays

5

[ ]

X[0.025]=

[ ]

X[0.025]=

[ ]

X[0.025]=

NAC #1

[ ]

X[ ]=

NAC #2

[ ]

X[ ]=

NAC #3
NAC #4

Current Draw from

TB9 (nonalarm)

[ ]=

[ ]=

[ ]=

Sum each column

6

for totals

Primary Non-Alarm =

Secondary Alarm =

Secondary Non-Alarm =

Table 5.3 System Current Draw Calculations

1 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add

another 0.005 amps.

2 The current shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes 0.040

amps.

3 Refer to the Device Compatibility Document for standby current.
4 Enter the number of IDCs used minus one.
5 Must use compatible listed Power Supervision Relay.
6 Total current draw listed above cannot exceed 7.2 amps