MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

NFPA Standard-Specific Requirements

NFPA 72 Auxiliary Fire Alarm System

NFPA 72 Remote Station Protective Signaling System

Notes:

1. Cut Jumper JP30 on the MRP-2002 main circuit board to supervise placement of the 4XTMF

module.

2. Refer to “4XTMF Municipal Box Transmitter Option Module” on page 33 for detailed

information.

RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.

+ -

Polarity Shown is
Normal Standby

4XTMF Transmitter Module

Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.

Power limited

Figure C.3 Remote Station Connection Using 4XTMF Module

+

-

(Dummy load with a 4.7K

, ¼ watt resistor

when no connection is made)