B.1 template 1: cross-zone system - with horn, B.1: template 1: cross-zone system - with horn – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 119

Advertising
background image

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

119

Template 1: Cross-Zone System - With Horn

FACP Configuration Templates

B.1 Template 1: Cross-Zone System - With Horn

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).

Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-
cuit (input zone activation will activate the corresponding output circuit) and c indicates that the
output circuit will indicate when one or more inputs of a cross-zoned group have been activated
(refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 66).

Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the same
Release Circuit number must be active at the same time to turn on the corresponding Release output
circuit.

Input Zone Types:

Zone 1 = circuit with type code of 2-wire smoke

Zone 2 = circuit with type code of 2-wire smoke

Zone 3 = circuit with type code Manual Release - activation will cause an immediate agent
release

Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Type
operation (refer to “Abort Type” on page 71)

Zone 5 = circuit with type code of Pull Station

Zone 6 = circuit with type code of Supervisory

Output Circuit Types:

Output 1 = Release Circuit 1 - Unsupervised for shorts

Output 2 = Horn NAC - silenceable, programmed for cross-zone coded operation for Release
Circuit 1 (refer to Cross Zone in the section titled “Coded NAC Operation” on page 98

Output 3 = Alarm NAC - silenceable, coded for steady on

Output 4 = Alarm NAC - silenceable, coded for steady on

Timers

Pre-Discharge Delay - set for 30 seconds

Discharge - set for 1 minute

Waterflow Delay Timer - set for 90 seconds

AC Loss Delay Timer - set for 2 hours

Template 1: Cross-Zone System with Horn

INPUT ZONES

1

2

3

4

5

6

OUTPUT CIRCUITS

2-WIRE

SMOKE

2-WIRE

SMOKE

MANUAL

RELEASE

ABORT

PULL

STATION

SUPERVISORY

#1 RELEASE CIRCUIT 1

C1

C1

X

X

X

#2 HORN NAC

Xc

Xc

X

#3 ALARM NAC

X

#4 ALARM NAC

X

X

X