FACP Configuration Templates

Template 1: Cross-Zone System - With Horn

FACP Operation

Input Zone 1 (2-Wire Smoke) Activation only:
Output 2 (Horn NAC) will pulse 1 second on and 1 second off.
Output 4 (Alarm NAC) will turn on steady.

Input Zone 2 (2-Wire Smoke) Activation only:
Output 2 (Horn NAC) will pulse 1 second on and 1 second off.
Output 4 (Alarm NAC) will turn on steady.

Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) begins agent release and the Discharge Timer will begin to count
down. When the Discharge Timer reaches 0, Output 1 will turn off the agent release
Output 2 (Horn NAC) will turn on steady
Output 4 (Alarm NAC) will turn on steady

Input Zone 4 (Abort Release Switch) Activation only:
Pre-Discharge Timer will continue to count down until it reaches 10 seconds and then stop.
Releasing the Abort Release Switch will allow the Pre-Discharge Timer to continue its count
down from 10 second. If the Abort Release Switch is again activated before the Pre-Discharge
Timer reaches 0, the Timer will reset to 10 seconds and hold.

Input Zone 5 (Pull Station) Activation only:
Output 1 (Release Circuit 1) begins agent release and the Discharge Timer will begin to count
down. When the Discharge Timer reaches 0, Output 1 will turn off the agent release
Output 3 (Alarm NAC) turns on steady

Input Zone 6 (Supervisory) Activation only:
No output circuits will be activated. FACP will indicate a supervisory condition

Input Zone 1 (2-Wire Smoke) and Input Zone 2 (2-Wire Smoke) Activation together:
In addition to the individual events that will occur for each Input Zone as detailed above, the
Pre-Discharge Timer will begin to count down. Output 2 will pulse at a ½ second on and ½
second off rate while the Pre-Discharge Timer is counting down. When the Pre-Discharge
Timer reaches 0, Output 1 (Release Circuit 1) will begin the agent release, Output 2 will turn
on steady and the Discharge Timer will begin to count down. When the Discharge Timer
reaches 0, Output 1 will turn off the agent release.

FACP Relay Operation

The following description of FACP relay operations are in addition to normal system operation.

Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire Smoke) or Zone 3
(Manual Release) or Zone 5 (Pull Station) will operate Alarm Relay

Trouble Relay - any system trouble will activate the Trouble Relay

Supervisory - activation Input Zone 6 (Supervisory), the disabling of Releasing Circuit or any
other system supervisory will operate the Supervisory Relay