MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Installation

Input Circuits

Combination Manual Release/Abort

A combination Manual Release/Abort circuit allows an FACP to distinguish between a manual
release pull station and an abort switch installed on the same circuit. Any circuit can be pro-
grammed as a Combo Type zone. The following figure illustrates the wiring of Zone 2 as a Style B
(Class B) Manual Release/Abort circuit.

Requirements for the Combination Manual Release/Abort circuit are as follows:

The manual release pull station must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.7.

The Abort Switch must connect to the FACP Initiating Device Circuit after the In-Line
Resistor as shown in Figure 2.7.

Program the FACP Initiating Device Circuit as a Manual Release/Abort combination circuit
as described in “Input Zones” on page 54.

Class B Initiating Device Circuits (supervised and power-limited)

4.7 K

, ½ watt resistor P/N:71252

In-Line-Resistor

1.2 K

, ½ watt resistor P/N: 75579

Manual release
pullstation

Dummy load all unused
circuits - 4.7 K

, ½ watt

resistor (P/N: 71245)

Figure 2.7 Style B Combination Circuit on Zone 2

Abort Switch

ms1

0ud

combo

IDC.cdr