MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

115

Input-to-Output Circuit Mapping and Cross-Zone Operation

Circuit Mapping and Cross-Zoning

Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output
circuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as
RELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is
programmed as a RELEASE 2.

Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.

Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.

Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus

Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.

Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm
NAC) but not Output Circuits 2, 3 or 4.

Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate Output
Circuit 2 (Release 1) but not Output Circuits 3 or 4.

Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate Output
Circuit 3 (Release 2) but not Output Circuits 2 or 4.

ZONE 1 TYPE

1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV

OUTPUT MAP ZONE 1

1=ALARM NAC YES
2=RELEASE 1 YES
3=RELEASE 2 NO

OUTPUT MAP ZONE 1

1=SUPV BELL NAC N/A

REL 1 CROSS GROUP 1

1=ZONE 1 YES
2=ZONE 2 YES
3=ZONE 3 NO

OUTPUT MAP ZONE 2

1=SUPV BELL NAC N/A

ZONE 2 TYPE

1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV

OUTPUT MAP ZONE 2

1=ALARM NAC YES
2=RELEASE 1 YES
3=RELEASE 2 NO

ZONE 3 TYPE

1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV

ZONE 4 TYPE

1=WATERFLOW NS
2=COMBO
3=COMBO W/AR. SUPERV

OUTPUT MAP ZONE 3

1=ALARM NAC YES
2=RELEASE 1 NO
3=RELEASE 2 YES

OUTPUT MAP ZONE 3

1=SUPV BELL NAC N/A

OUTPUT MAP ZONE 4

1=SUPV BELL NAC N/A

OUTPUT MAP ZONE 4

1=ALARM NAC YES
2=RELEASE 1 NO
3=RELEASE 2 YES

REL 2 CROSS GROUP 1

1=ZONE 1 NO
2=ZONE 2 NO
3=ZONE 3 YES

REL 2 CROSS GROUP 1

1=ZONE 4 YES
2=ZONE 5 NO
3=ZONE 6 NO