Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 62

Advertising
background image

62

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Programming

Master Programming Level

Pressing the down arrow key while viewing the Edit Output Type Screen will display additional
screens with the following types:

• Release Circuit 1
• Release Circuit 2
• Alarm NAC
• Waterflow NAC
• Release Stage Coded NAC (Refer to “Release Stage/NAC Operation” on page 98.)
• Release Stage Discharge NAC (Refer to “Release Stage/NAC Operation” on page 98.)
• Release Stage Pre-Discharge NAC (Refer to “Release Stage/NAC Operation” on page 98.)
• Horn NAC
• Strobe NAC
• Supv Bell NAC
• Trouble Bell NAC

Press the number key corresponding to the desired Output Type to program the selected Output.

Release Circuit 1 or Release Circuit 2

If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreen
will be displayed:

This screen allows the programmer to select whether or not to supervise the Releasing Circuit
Output for shorts.

UNSUPV SHORTS - this option should normally be selected when a releasing solenoid is
connected to the output so the solenoid coil is not supervised for shorts

SUPV SHORTS - this option, which supervises for shorts, should only be selected when the
REL-4.7K option is installed in series with the solenoid coil.

Release Stage NAC

If Release Stage Coded, Release Stage Discharge or Release Stage Pre-Discharge is selected as the
Output Type, the following subscreen will be displayed:

EDIT RELEASE CIR #

1=UNSUPV SHORTS

2=SUPV SHORTS

NOTE: Release circuits may be directly activated by a single input zone or may be activated
using cross-zoned inputs. Refer to “Circuit Mapping and Cross-Zoning” on page 112 for a
description of cross-zoning and input to output circuit mapping.

RELEASE STAGES

1=RELEASE 1 ONLY

2=RELEASE 2 ONLY