R to table 3.1 on, To table 3.1 on – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 56

Advertising
background image

56

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Programming

Master Programming Level

Pressing the down arrow key displays additional zone types as indicated in the following table.

While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.

Zone Type

Action When Activated

Pull-Station

Fire Alarm

Manual Release

1

1 Activation of a Manual Release Switch will override Predischarge Delay and override

an active Abort Release Switch, resulting in an immediate agent release.

Fire Alarm

Manual Release/Abort

1

5

Fire Alarm

Discharge Pressure

2

2 Discharge Pressure Switch can be mapped to one or both Release Circuits, but it will

not activate them. The following will occur when it is avtivated:

Alarm LED flashes 1/2 second on, 1/2 second off

Discharge LED turns on steady



Alarm Relay(s) activate

Momentarily activate/energize any relay programmed as a pre-discharge relay

Activate any relay programmed as a discharge relay

Turn on all enabled and mapped NACs

Display an active IDC message on FACP display and send message to printer/pc



Turn on FACP piezo

Fire Alarm

Normally Open Contact

Fire

N/A
N/A
N/A

Waterflow

Fire

Waterflow NS (nonsilenceable)

Fire, nonsilenceable

Combo

Fire/Supervisory

Combo w/AutoResettable Superv

3

3 AutoResettable means that a device with this type code, when activated, will automat-

ically reset when the corresponding condition is cleared.

Fire/Supervisory, nonlatching

2-Wire Smoke

Fire Alarm

2-Wire Heat

Fire Alarm

N/A

Linear Heat

Fire Alarm

N/A
N/A
Fire

Fire Alarm

Low Pressure

Supervisory, latching

Low Pressure AutoResettable

3

Supervisory, nonlatching

High Pressure

Supervisory

High Pressure AutoResettable

3

Supervisory, nonlatching

Disable Release

4

4 Disable Release allows the installer to disable the releasing solenoids during system

testing. Disable Release will only work when the system is not in alarm.

Supervisory, nonlatching (disables Release Circuits)

Supervisory

Supervisory, latching

Supervisory AutoResettable

3

Supervisory, nonlatching

Abort Release Switch

5

5 Activation of an Abort Release Switch during system normal operation (non-alarm)

results in an audible and visual indication at the FACP. If the Abort Switch is pressed
and then the Manual Release is activated, the Manual Release will over-ride the Abort
and cause an immediate release. If Manual Release is activated and then Abort
Switch is pressed, the Abort Switch will have no effect.

Supervisory, nonlatching

N/A

Table 3.1 Zone Types