MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

129

Template 4: Single Hazard - Count One

FACP Configuration Templates

AC Loss Delay Timer - set for 2 hours

FACP Operation

Input Zone 1 (2-Wire Smoke) Activation:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 2 (Alarm NAC) will turn on steady until discharge. Turns off upon discharge.
Output 3 (Alarm NAC) will pulse 1 second on, 1 second off until discharge, then turns on
steady.
Output 4 (Release Stage Discharge) will turn on steady upon discharge.

Input Zone 2 (2-Wire Smoke) Activation:
Output 1 (Release Circuit 1) will perform an agent release following a 30 second Pre-
Discharge delay and remains on until panel reset.
Output 2 (Alarm NAC) will turn on steady until discharge. Turns off upon discharge.
Output 3 (Alarm NAC) will pulse 1 second on, 1 second off until discharge, then turns on
steady.
Output 4 (Release Stage Discharge) will turn on steady upon discharge.

Input Zone 3 (Manual Release) Activation only:
Output 1 (Release Circuit 1) begins agent release and remains on until reset.
Output 3 (Alarm NAC) will turn on steady.
Output 4 (Release Stage Discharge) will turn on steady.

Input Zone 4 (Abort Release Switch) Activation only:
Pre-Discharge Timer will continue to count down until it reaches 10 seconds and then stop.
Releasing the Abort Release Switch will allow the Pre-Discharge Timer to continue its count
down from 10 second. If the Abort Release Switch is again activated before the Pre-Discharge
Timer reaches 0, the Timer will reset to 10 seconds and hold.

Input Zone 5 (Discharge Pressure Switch) Activation:
Output 3 (Alarm NAC) will turn on steady.
Output 4 (Release Stage Discharge) will turn on steady

Input Zone 6 (Supervisory) Activation only:
No output circuits will be activated. FACP will indicate a supervisory condition

FACP Relay Operation

The following description of FACP relay operations are in addition to normal system operation.

Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire
Smoke) or Zone 3 (Manual Release) or Zone 5 (Discharge Pressure Switch) will operate Alarm
Relay

Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay

Supervisory (Tracking) - activation Input Zone 6 (Supervisory), the disabling of Releasing
Circuit or any other system supervisory will operate the Supervisory Relay