Master Programming Level

Programming

Pressing 2 while viewing the Discharge Setup screen will cause the following screen to be
displayed:

A Discharge Time of 01 to 20 minutes can be programmed. A flashing cursor is positioned in the
lower left corner of the display. Enter a Discharge time consisting of two digits, such as 05 for five
minutes. Upon entering the second digit, the time will be stored in the control panel memory and
the display will return to the Delay Screen which will indicate the new Discharge time. In this
example, when the corresponding agent releasing circuit is activated, it will continue an agent
release for five minutes after activation.

Note that if a Manual Release is activated, the Discharge Timer will be activated and the release
will continue for the duration of the Discharge Timer.

Waterflow Delay

A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
in delays of the waterflow device. The factory default setting for Waterflow delay is 00 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1 to display the following screen:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.

AC Loss Delay

The reporting of a loss of AC power can be delayed by programming the length of the desired
delay. Press 1 while viewing Timer Screen #2 to display the following:

DISCHARGE

RANGE 01-20 MINUTES

Pre-Discharge Setup Screen

TIMER

1=PRE-DISCHARGE1 030
2=PRE-DISCHARGE2 030
3=DISCHARGE1 1MIN

Timer Screen #1

WATERFLOW DELAY

RANGE 00-90 SECONDS

Waterflow Delay Screen

TIMER

1=DISCHARGE2 1MIN
2=WATERFLW DELAY 20S
3=AC LOSS DELAY 2HR

Timer Screen #2

AC LOSS DELAY

RANGE 00-24 HOURS

AC Loss Delay Screen #1