6 system setup, System setup – Fire-Lite MRP-2002C Agent Release Control Panel User Manual

Page 70

Advertising
background image

70

MRP-2002 Series Instruction Manual — P/N 53049:E2 3/7/2013

Programming

Master Programming Level

3.5.6 System Setup

System Setup allows the programmer to configure the following control panel features:

Abort Type: Pressing an Abort Switch will interrupt agent releasing during an alarm condition.
Releasing the Abort Switch will resume the agent release.

Timers: This option allows the programmer to set the Pre-Discharge, Discharge, Waterflow
and AC Loss time delays.

Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout to a user defined readout when the control panel is in Normal condition.

Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory.

Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. If the Trouble
Reminder
feature is not enabled and a trouble condition is not cleared within 24 hours, the
panel will reactivate the trouble sounder and send an Abnormal 24 hour Test message via the
optional communicator.

Charger Disable: This option allows the programmer to disable the onboard battery charger in
the event an external battery charger is being used.

Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to “Canadian Option” on page 77).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.

ANN-SECONDARY: This option allows the use of a secondary ANN-BUS with the ANN-SEC
option module. This option must be enabled if the ANN-SEC option card is installed on J13 of
the main circuit board.

Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:

PROGRAMMING

1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP

Programming Screen #2

SYSTEM SETUP

1=ABORT TYPE

2=TIMERS

3=BANNER

System Setup Screen #1

SYSTEM SETUP

1=TIME-DATE

2=TROUBLE REMIND NO

3=CHARGR DISABLE NO

System Setup Screen #2

SYSTEM SETUP

1=CANADIAN OPTION OFF

2=SEC ANN ENABLE NO

System Setup Screen #3

Advertising
This manual is related to the following products: