C2. current input X
C2.
current input X
X stands for connection terminal A or B
stands for Fct. no. C2.2 (A) / C2.3 (B)
C2. .1
range 0%…100%
Fixed current range (4...20 mA) for the assigned value range; The range
indicated cannot be changed.
C2. .2
extended range
Adjustable, extended, linear range goes from 3.6...21.0 mA;
Error ranges: 0.5...<3.6 mA / >21.0...23.0 mA / <0.5 mA open circuit / >23.0
closed circuit
C2. .3
measurement
The connected sensor delivers the values to the current input; possible
values: temperature, pressure or current
C2. .4
range
Measuring range from 0...100% in the corresponding unit.
C2. .5
time constant
Range: 000.1…100 s
C2. .6
information
Serial no. of the I/O board, software version no. and production date of the
circuit board
C2. .7
simulation
Sequence see B 1. current input X
C2. .8
4mA trimming
Trimming of the current at 4 mA
Reset to 4 mA restores the factory calibration.
C2. .9
20mA trimming
Trimming of the current at 20 mA
Reset to 20 mA restores the factory calibration.