Electrical connections – KROHNE IFC 300 Converter EN User Manual
Page 91

ELECTRICAL CONNECTIONS
4
91
IFC 300
www.krohne.com
08/2010 - 4000069803 - MA IFC 300 R04 en
Status output / limit switch active, modular I/Os
• Observe connection polarity.
• U
int
= 24 VDC
• I ≤ 20 mA
• R
L
≤ 47 kΩ
• open:
I ≤ 0.05 mA
closed:
U
0, nom
= 24 V at I = 20 mA
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
Status output / limit switch passive, modular I/Os
• Any connection polarity.
• U
ext
= 32 VDC
• I ≤ 100 mA
• R
L, max
= 47 kΩ
R
L, min
= (U
ext
- U
0
) / I
max
• open:
I ≤ 0.05 mA at U
ext
= 32 VDC
closed:
U
0, max
= 0.2 V at I ≤ 10 mA
U
0, max
= 2 V at I ≤ 100 mA
• The output is open when the device is de-energized.
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
Figure 4-54: Status output / limit switch active S
a
Figure 4-55: Status output / limit switch passive S
p