Operation, 4 set free units – KROHNE IFC 300 Converter EN User Manual
Page 133

OPERATION
6
133
IFC 300
www.krohne.com
08/2010 - 4000069803 - MA IFC 300 R04 en
6.3.4 Set free units
C5.8 HART
C5.8
HART
This function is only available for devices with a HART
®
interface!
C5.8.1
HART
Switch HART
®
communication on/off:
Select:
on (HART
®
active) current = 4…20 mA /
off (HART
®
not active) current = 0…20 mA
C5.8.2
address
Set address for HART
®
operation.
Select: 00 (point-to-point operation, current output has normal function,
current = 4…20 mA) / 01...15 (Multi-Drop operation, current output has a
constant setting of 4 mA)
C5.8.3
message
Set required text:
A…Z ; a…z ; 0…9 ; / - + , . *
C5.8.4
description
Set required text:
A…Z ; a…z ; 0…9 ; / - + , . *
C5.9 quick setup
C5.9
quick setup
Activate quick access in quick setup menu; default setting: quick setup is
active (yes)
Select: yes (switched on) / no (switched off)
C5.9.1
reset counter 1
Reset counter 1 in quick setup menu?
Select: yes (activated) / no (switched off)
C5.9.2
reset counter 2
Reset counter 2 in quick setup menu?
Select: yes (activated) / no (switched off)
C5.9.3
reset counter 3
Reset counter 3 in quick setup menu?
Select: yes (activated) / no (switched off)
C5.9.4
process input
Activate quick access to the important process input parameters
Select: yes (activated) / no (not activated)
Free units
Sequences to set texts and factors
Texts
Texts
Texts
Texts
Volume flow, mass flow and density:
3 digits before and after the slash
xxx/xxx (max. 3 digits before / after the slash)
Volume, mass:
xxx (max. 3 digits)
Permissible characters:
A…Z ; a…z ; 0…9 ; / - + , .*; @ $ % ~ () [] _
Conversion factors
Conversion factors
Conversion factors
Conversion factors
Desired unit
= [unit see above] * conversion factor
Conversion factor
Max. 9 digits
Shift decimal point:
↑ to the left and ↓ to the right