OPERATION

6

129

IFC 300

www.krohne.com

08/2010 - 4000069803 - MA IFC 300 R04 en

No.

Function

Settings / descriptions

C4 I/O HART

C4

I/O HART

Selection / display of the 4 dynamic variables (DV) for HART

®

.

The HART

®

current output (terminal A basic I/Os or terminal C modular I/Os)

always has a fixed link to the primary variables (PV). Fixed links of the other

DVs (1-3) are only possible if additional analogue outputs (current and

frequency) are available; if not, the measurement can be freely selected

from the following list: in Fct. A4.1 "measurement".

…

stands for 1, 2, 3 or 4

X stands for connection terminals A...D

C4.1

PV is

Current output (primary variable)

C4.2

SV is

(secondary variable)

C4.3

TV is

(tertiary variable)

C4.4

4V is

(4th variable)

C4.5

HART units

Changes units of DVs (dynamic variables) in the display

Break: return with ^ key

HART display

®

: copies the settings for the display units to the settings for

DVs

Standard: sets factory defaults for DVs

C4.….1

current out X

Shows the current analogue measured value of the linked current output.

The measurement cannot be changed!

C4.….1

frequency out X

Shows the current analogue measured value of the linked frequency output,

if present. The measurement cannot be changed!

C4.….1

HART dynamic var.

Measurements of the dynamic variables for HART

®

.

Linear measurements: volume flow / mass flow (not

not

not

not valid for PF (partly

filled)) / diagnosis value / flow speed / coil temperature / conductivity (not

not

not

not

valid for PF (partly filled) and CAP (capacitive)) / level (only

only

only

only valid for PF

(partly filled))

Digital measurements: counter 1 / counter 2 / counter 3 / operating hours

No.

Function

Settings / descriptions

C5 device

C5.1 device info

C5.1

device info

Grouping of all functions that have no direct effect on the measurement or

any output.

C5.1.1

Tag

Settable characters (max. 8 digits):

A…Z; a…z; 0…9; / - , .

C5.1.2

C number

CG number, non-alterable (input/output versions)

C5.1.3

device serial no.

Serial no. of the system.

C5.1.4

electronic serial no.

Serial no. of the electronic assembly, cannot be changed.

C5.1.5

SW.REV.MS

Serial no. of the circuit board, version no. of the main software, production

date of the circuit board

C5.1.6

Electronic Revision ER

Reference identification number, electronic revision and production date of

the device; includes all hardware and software changes