Electrical connections – KROHNE IFC 300 Converter EN User Manual

Page 67

Advertising
background image

ELECTRICAL CONNECTIONS

4

67

IFC 300

www.krohne.com

08/2010 - 4000069803 - MA IFC 300 R04 en

Power supply connection (excluding 19" rack-mounted housing)

1 100...230 VAC (-15% / +10%), 22 VA
2 24 VDC (-55% / +30%), 12 W
3 24 VAC/DC (AC: -15% / +10%; DC: -25% / +30%), 22 VA or 12 W

Power supply connection for 19" rack-mounted housing (28 TE)

Power supply connection for 19" rack-mounted housing (21 TE)

INFORMATION!
For safety reasons the manufacturer has connected the 28d contacts internally to the 28z, 30z
and 32z contacts. You are advised to also connect contacts 28z, 30z and 32z to the external
protective conductor.

CAUTION!
The protective conductor contacts must not be used to loop through the PE connection.