4 digital signals (event traces), Digital signals (event traces), 2 device description – West Control Solutions DataVU 5 User Manual

Page 15

Advertising
background image

15

2 Device description

2.4 Digital signals (event traces)

Signal types

In addition to the four binary inputs (extra code), digital signals generated by
the instrument itself can also be displayed in the six digital traces (event
traces):

signal

Description

Binary input 1 — 4

Four binary inputs available as hardware
(extra code)

Logic channel 1 — 6

Channels which are created by using the math
and logic module (extra code required)

Low alarm 1 — 6

Underrange of the channels

Low combination alarm

OR linkage of all low alarms

High alarm 1 — 6

Overlimit of channels

High combination alarm

OR linkage of all high alarms

Counter/integrator alarm 1 — 6

Limit infringements of counter and
integrator channels (extra code required)

Counter/integrator combination
alarm

OR linkage of all counter/integrator
alarms (extra code required)

Combination alarm

OR linkage of all low, high and counter/inegrator
alarms

CF card inserted

The signal is set when a CF card is inserted in the
instrument. It remains active until the card is
removed.

Int. mem. alarm/CF card

The alarm is triggered when the internal storage
memory available for read-out via the CF card
card has fallen below a certain value

1

.

1

The limit for all memory alarms is the same, and is set by the parameter
Configuration

Device data Memory alarm.

Int. mem. alarm/serial

The alarm is triggered when the internal storage
memory available for read-out via the interface
has fallen below a certain value

1

.

Mem. alarm/CF card

The alarm is triggered when the storage memory
available on the CF card that has been plugged in
falls below a certain value

1

, or no CF card is

plugged in.

Error

Alarm when the battery is empty, or the time has
to be set.

Chapter 3.7 “Device info”

MODbus flag

Control flag, which can be activated through one
of the interfaces.