4 Configuration parameters

64

4.2.3 Configuration - Analog inputs

Enable options

Configuration
➔ Device data

➔ Enable options

This parameter is used to
enable additional
functions, e.g. the math/
logic module and counter/
integrator. The parameter
will not be available if all
the recorder functions have
been enabled.

Enable options:
Computed code
No.

Configuration
➔ Device data

➔ Enable options

➔ Computed

code No.

(display a code No.)

The value that is shown
here must be passed on to
the manufacturer. The
manufacturer will then
send you the release code.

Enable options:
Authorization code

Configuration
➔ Device data

➔ Enable options

➔ Authorization

code

Authorization code
entry

Enter the authorization
code (release code) you
received here.

Device-info text

In the setup program, the parameter Configuration level

Device data can be used

to enter a device-Info text (max. 500 characters). The text is saved together with the
measurement data, and can be displayed in the PCA3000 evaluation software. The
text will not be shown on the instrument.

Parameter

Value/Selection

Description

Sensor

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Sensor

Off,
RTD,
Thermocouple,
Current,
Voltage

Depending on the sensor
that was selected, only the
relevant parameters can be
selected when configuring
the analog input.

Linearization

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Linearization

Linear, Pt100, Pt100 JIS,
Pt100 GOST, Pt500,
Pt1000, Pt50, Ni100,
Cu50, Cu100, Fe-Con J,
NiCr-Con E, NiCr-Ni K,
NiCrSi N, Cu-Con T,
PtRh-PtRh B,
PtRh-Pt R, PtRh-Pt S,
Cu-Con U, Fe-Con L,
W3W25Re D,
W5W26Re C,
ChromelCopel

Connection circuit

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Connection circuit

2 — 4 wire

Only for sensor type:
resistance thermometer

Cold junction

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Cold junction

Intern.Pt100
Extern. const

Parameter

Value/Selection

Description