STANDARD FEATURES
Electrical
Dedicated weatherproof electrical power and controls panels are situated at the end of the
unit and contain:
Emergency Stop fitted to controls compartment door
Separate, fully accessible, controls compartment, allowing adjustment of control set
points whilst the unit is operational
Circuit breakers for protection of all major unit components
Separate door locking electrical isolation for each mains compartment
Electrical terminals for external evaporator pipework trace heating (230V/500W)
are provided.
CAUTION
A fused and isolated electrical supply of the appropriate phase, frequency and
voltage should be installed.
The electrical power and control panel is wired to the latest European standards and
codes of practice.
Mains supply is 3 phase and a neutral is not required. Refer to
OPTIONAL EXTRAS
– ENERGY SAVING
Power Factor Correction
When applied to the motors of each compressor, the compressor power factor is
controlled to a minimum operating value of 0.95 at the full operating capacity. This
satisfies many supply authorities that may impose surcharges on equipment with power
factor less than 0.95.
OPTIONAL EXTRAS
– GENERAL
Corrosion Resistant
Coated Coils
In atmospheres where high corrosion is anticipated a corrosion resistant coating is applied
to the aluminium fins of either phenolic or epoxy, dependent upon size.
Coil Guards
Guards can be fitted to each of the outer coils to protect against damage.