Electrical data, Ultima compact freecool chillers, General specification – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 46: Chillers

Advertising
background image

ULTIMA COMPACT FREECOOL

Chillers

46

Chillers

Technical Manual : 6259576 V1.2.0_02__2013

General Specification

ELECTRICAL DATA

UCFC75D-2/1

UCFC100D-2/1

UCFC125D-3/1

UCFC150D-3/1

UCFC160D-6/2

Unit Data

(1)

Nominal Run Amps

A

50

62

79

93

99

Maximum Start Amps

A

140

167

217

246

252

Rec Mains Fuse Size

A

63

80

125

125

125

Mains Supply

VAC

400V / 3PH / 50 Hz

Max Mains Incoming Cable Size

mm²

70 (direct to

MCCB)

70 (direct to

MCCB)

70 (direct to

MCCB)

70 (direct to

MCCB)

Direct to Bus Bar

Permanent Supply

VAC

230V / 1PH + N / 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Immersion Heater Rating

W

40

40

80

80

100

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

Fan & Motor - Per Fan

Quantity

2

2

3

3

6

Full Load Amps

A

1.75

1.75

1.75

1.75

1.75

Locked Rotor Amps

A

6.20

6.20

6.20

6.20

6.20

Motor Size

kW

0.98

0.98

0.98

0.98

0.98

Compressor - Per
Compressor

(1)

Quantity

4

4

2 + 2

4

4

Motor Size

kW

6.2

8.1

8.1 / 11.7

11.7

11.7

Nominal Run Amps

A

11.7

14.6

14.6 / 22.0

22.0

22.0

Oil Heater Rating

W

65.0

65.0

65.0 / 75.0

75.0

75.0

Start Amps

(2)

A

98.0

120.0

120.0 / 175.0

175.0

175.0

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

(1)

Nominal Run Amps

A

48

55

71

85

91

Maximum Start Amps

(2)

A

140

167

217

246

252

Recommended Mains Fuse

A

63

80

125

125

125

Compressor Nominal Run
Amps - Per Compressor

A

4 x 11

4 x 13

2 x 20 / 2 x 13

4 x 20

4 x 20

Electronic Soft-Start

(1)

Nominal Run Amps

A

50

62

79

93

99

Maximum Start Amps

(2)

A

97

119

147

176

182

Recommended Mains Fuse

A

63

80

125

125

125

Water Pump

(1)

Single Head or Run/Standby
- Standard

Unit Nominal Run Amps

A

55

67

86

98

113

Recommended Mains Fuse

A

80

100

125

125

160

Motor Size

kW

2.2

2.2

3.0

3.0

7.5

Full Load Amps

A

4.8

4.8

6.8

6.8

14.7

Single Head or Run/Standby
-Larger

Unit Nominal Run Amps

A

57

69

85

108

120

Recommended Mains Fuse

A

80

100

125

125

160

Motor Size

kW

3.0

3.0

7.5

7.5

11

Full Load Amps

A

6.8

6.8

15.5

15.5

21.4

Twin Head - Standard

Unit Nominal Run Amps

A

56

68

85

99

113

Recommended Mains Fuse

A

80

100

125

125

160

Motor Size

kW

3.0

3.0

3.0

3.0

7.5

Full Load Amps

A

6.1

6.1

6.1

6.1

14.7

Twin Head - Larger

Unit Nominal Run Amps

A

56

70

87

102

120

Recommended Mains Fuse

A

80

100

125

125

160

Motor Size

kW

3.0

4.0

4.0

4.0

11

Full Load Amps

A

6.1

7.7

7.7

7.7

21.4

(1)

Based at 12/7°C water and 30°C ambient with standard ac type fans.

(2)

Starting amps refers to the Star connection only with standard ac type fans.