Positioning, Chillers ultima compact freecool, Installation data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 57

Advertising
background image

Chillers

ULTIMA COMPACT FREECOOL

Chillers

57

Technical Manual : 6259576 V1.2.0_02__2013

Installation Data

POSITIONING

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly

Levelling should be to +/- 5mm

Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections

Observe airflow and maintenance clearances

Pipework and electrical connections are readily accessible

Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity

Within a side enclosed installation, the fan MUST be higher than the
enclosing structure

Figures in brackets indicate airflow and maintenance clearances for side-enclosed or
multiple chiller applications

Ensure there are no obstructions directly above the fans

Allow free space above the fans to prevent air recirculation

CAUTION

Prior to connecting services, ensure that the equipment is installed and
completely level.

The Sound Pressure data quoted (refer to

Sound Data

, on page 37 ) is only valid in free

field conditions, where the unit is installed on a reflective base. If the equipment is placed
adjacent to a reflective wall, values may vary to those stated in our Performance Data
section, typically increasing by 3dB(A) for each side added.

Airflow & Maintenance
Clearances:


1 = 1.0m (2.0m)
2 = 1.0m (1.8m)

1

2

2

1