Ultima compact freecool chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 50: Electrical data

Advertising
background image

ULTIMA COMPACT FREECOOL

Chillers

50

Chillers

Technical Manual : 6259576 V1.2.0_02__2013

General Specification

ELECTRICAL DATA

UCFC300D-8/2

UCFC330D-10/2

UCFC360D-10/2

UCFC400D-12/2

UCFC450D-12/2

Unit Data

(1)

Nominal Run Amps

A

173

198

216

240

260

Maximum Start Amps

A

454

435

453

520

540

Rec Mains Fuse Size

A

250

250

315

315

355

Mains Supply

VAC

400V / 3PH / 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Permanent Supply

VAC

230V / 1PH + N / 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Immersion Heater Rating

W

100

100

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

Fan & Motor - Per Fan

Quantity

8

10

10

12

12

Full Load Amps

A

1.75

1.75

1.75

1.75

1.75

Locked Rotor Amps

A

6.20

6.20

6.20

6.20

6.20

Motor Size

kW

0.98

0.98

0.98

0.98

0.98

Compressor - Per
Compressor

(1)

Quantity

4

3 + 3

6

3 + 3

6

Motor Size

kW

22.8

18.2 / 15.0

18.2

22.8 / 18.2

22.8

Nominal Run Amps

A

40.0

33.0 / 27.0

33.0

40.0 / 33.0

40.0

Oil Heater Rating

W

130.0

130.0 / 130.0

130.0

130.0 / 130.0

130.0

Start Amps

(2)

A

320.0

270.0 / 215.0

270.0

320.0 / 270.0

320.0

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1)

A

442

420

438

503

521

Maximum Start Amps

(2)

A

250

250

250

315

315

Recommended Mains Fuse

A

4 x 36

3 x 30 / 3 x 24

6 x 30

3 x 36 / 3 x 30

6 x 36

Compressor Nominal Run
Amps - Per Compressor

A

158

180

198

219

237

Electronic Soft-Start

(1)

Nominal Run Amps

A

173

198

216

240

260

Maximum Start Amps

(2)

A

326

327

345

392

412

Recommended Mains Fuse

A

250

250

315

315

355

Water Pump

(1)

Single Head or Run/Standby
- Standard

Unit Nominal Run Amps

A

188

212

230

254

275

Recommended Mains Fuse

A

250

315

315

315

355

Motor Size

kW

7.5

7.5

7.5

7.5

7.5

Full Load Amps

A

14.7

14.7

14.7

14.7

14.7

Single Head or Run/Standby
-Larger

Unit Nominal Run Amps

A

195

219

237

261

282

Recommended Mains Fuse

A

250

315

315

315

355

Motor Size

kW

11

11

11

11

11

Full Load Amps

A

21.4

21.4

21.4

21.4

21.4

Twin Head - Standard

Unit Nominal Run Amps

A

188

212

230

254

275

Recommended Mains Fuse

A

250

315

315

315

355

Motor Size

kW

7.5

7.5

7.5

7.5

7.5

Full Load Amps

A

14.7

14.7

14.7

14.7

14.7

Twin Head - Larger

Unit Nominal Run Amps

A

195

219

237

261

282

Recommended Mains Fuse

A

250

315

315

315

355

Motor Size

kW

11

11

11

11

11

Full Load Amps

A

21.4

21.4

21.4

21.4

21.4

(1)

Based at 12/7°C water and 30°C ambient with standard ac type fans.

(2)

Starting amps refers to the Star connection only with standard ac type fans.