Global & directional sound level, Ultima compact freecool chillers, Sound data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 38: Chillers, Standard - d models, Quiet - dq models

Advertising
background image

ULTIMA COMPACT FREECOOL

Chillers

38

Chillers

Technical Manual : 6259576 V1.2.0_02__2013

Sound Data

GLOBAL & DIRECTIONAL SOUND LEVEL

Standard - D Models

Sound Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

UCFC75D-2/1

Power

81

74

80

77

79

78

72

63

Pressure

@ 10m

49

42

48

45

47

46

40

31

UCFC100D-2/1

Power

81

80

84

78

79

78

72

63

Pressure

@ 10m

49

48

52

46

47

46

40

31

UCFC125D-3/1

Power

84

74

84

83

81

80

74

65

Pressure

@ 10m

52

42

52

51

49

48

42

33

UCFC150D-3/1

Power

84

74

84

83

81

80

74

65

Pressure

@ 10m

52

42

52

51

49

48

42

33

UCFC160D-6/2

Power

87

72

84

82

85

83

78

70

Pressure

@ 10m

55

40

52

50

53

51

46

38

UCFC180D-6/2

Power

87

75

84

82

85

83

78

71

Pressure

@ 10m

55

43

52

50

53

51

46

39

UCFC200D-6/2

Power

87

73

84

82

86

83

78

70

Pressure

@ 10m

55

41

52

50

54

51

46

38

UCFC225D-6/2

Power

88

75

84

82

86

84

78

71

Pressure

@ 10m

56

43

52

50

54

52

46

39

UCFC250D-8/2

Power

89

74

85

83

87

85

79

71

Pressure

@ 10m

57

42

53

51

55

53

47

39

UCFC275D-8/2

Power

89

76

85

83

87

85

80

73

Pressure

@ 10m

57

44

53

51

55

53

48

41

UCFC300D-8/2

Power

89

78

85

83

88

85

81

75

Pressure

@ 10m

57

46

53

51

56

53

49

43

UCFC330D-10/2

Power

90

77

86

84

88

86

80

73

Pressure

@ 10m

58

45

54

52

56

54

48

41

UCFC360D-10/2

Power

90

75

86

84

89

86

80

73

Pressure

@ 10m

58

43

54

52

57

54

48

41

UCFC400D-12/2

Power

91

78

87

85

89

87

82

75

Pressure

@ 10m

59

46

55

53

57

55

50

43

UCFC450D-14/2

Power

91

80

87

85

89

87

83

77

Pressure

@ 10m

59

48

55

53

57

55

51

45

Quiet - DQ Models

Sound Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

UCFC75DQ-2/1

Power

77

75

80

73

75

74

68

61

Pressure

@ 10m

45

43

48

41

43

42

36

29

UCFC100DQ-3/1

Power

79

81

85

75

77

75

70

63

Pressure

@ 10m

47

49

53

43

45

43

38

31

UCFC125DQ-3/1

Power

80

75

84

82

77

76

70

64

Pressure

@ 10m

48

43

52

50

45

44

38

32

UCFC150DQ-4/1

Power

81

76

85

82

79

77

71

65

Pressure

@ 10m

49

44

53

50

47

45

39

33

UCFC160DQ-6/2

Power

83

76

84

77

81

79

74

68

Pressure

@ 10m

51

44

52

45

49

47

42

36

UCFC180DQ-6/2

Power

83

76

84

77

82

79

74

68

Pressure

@ 10m

51

44

52

45

50

47

42

36

UCFC200DQ-6/2

Power

84

76

84

77

82

79

74

68

Pressure

@ 10m

52

44

52

45

50

47

42

36

UCFC225DQ-8/2

Power

85

78

85

78

84

80

75

69

Pressure

@ 10m

53

46

53

46

52

48

43

37

UCFC250DQ-8/2

Power

85

77

85

78

84

81

75

69

Pressure

@ 10m

53

45

53

46

52

49

43

37

UCFC275DQ-10/2

Power

86

79

86

79

85

81

77

71

Pressure

@ 10m

54

47

54

47

53

49

45

39

UCFC300DQ-10/2

Power

86

79

86

79

85

82

78

72

Pressure

@ 10m

54

47

54

47

53

50

46

40

UCFC330DQ-12/2

Power

86

79

87

80

85

82

77

71

Pressure

@ 10m

54

47

55

48

53

50

45

39

UCFC360DQ-12/2

Power

87

79

87

80

86

82

77

71

Pressure

@ 10m

55

47

55

48

54

50

45

39

UCFC400DQ-14/2

Power

87

80

88

81

86

83

79

73

Pressure

@ 10m

54

47

55

48

53

50

46

40

UCFC450DQ-14/2

Power

88

81

88

81

86

83

80

74

Pressure

@ 10m

55

48

55

48

53

50

47

41

1

dB(A) is the overall sound level, measured on the A scale.

2

All sound data measured at nominal conditions: Water in/out 12/7°C at 30°C ambient.

3

Figures based on standard unit, for units fitted with optional pump packages, please contact Airedale.

The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If the equipment is placed
adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for each side added.

Advertising
This manual is related to the following products: