Operating limits, Glycol data, Chillers ultima compact freecool – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 31: Performance data
Chillers
ULTIMA COMPACT FREECOOL
Chillers
31
Technical Manual : 6259576 V1.2.0_02__2013
Performance Data
OPERATING LIMITS
Unit With Electronic Fan Speed HP Control (-20°C)
Minimum Ambient air DB °C
-20°C
Maximum Ambient air DB °C
Refer to
Minimum leaving water temperature °C
+6C
Maximum return water temperature °C
+20°C
1
Temperatures lower than those stated can be obtained with additional glycol.
2
For conditions outside those quoted, please refer to Airedale.
GLYCOL DATA
For a given percentage of glycol in the system there are correction factors that need to
be applied, the following tables can be used as a guide.
CAUTION
All free cooling units should use minimum 20% glycol concentration.
Ethylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
20% / -9°C
30% / -15°C
40% / -23°C
Cooling Duty
Catalogue Data x by:
1.00
0.98
0.96
Input Power
1.00
0.98
0.97
Water Flow
1.00
1.09
1.12
Pressure Drop
1.00
1.29
1.48
Propylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
20% / -6°C
30% / -12°C
40% / -20°C
Cooling Duty
Catalogue Data x by:
0.98
0.94
0.91
Input Power
1.00
0.98
0.97
Water Flow
1.00
0.99
0.99
Pressure Drop
1.08
1.22
1.35
Example UCFC150DQ-4/1 operating at 7/12, 30°C Ambient, 30% Ethylene Glycol
Catalogue
Figure Multiplier
Corrected
Figure
Cooling kW
(refer to
146.1
x 0.98
30%
Ethylene
Glycol =
143.2 kW
Input kW
(refer to
54.1
x 0.98
53.0 kW
Flow l/s
calculated
(DX Mechanical Cooling kW)
7.49
x 1.09
8.16 l/s
T x 3.9
Pressure Drop kPa
(refer to
146
x 1.29
188 kPa