Interconnecting wiring, Chillers ultima compact freecool, Installation data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 61: Chillers, No pumps, Caution, With pumps

Advertising
background image

Chillers

ULTIMA COMPACT FREECOOL

Chillers

61

Technical Manual : 6259576 V1.2.0_02__2013

Installation Data

INTERCONNECTING WIRING

No Pumps

UCFC 75 - 450

L1

 

Mains incoming supply 400V / 3PH / 50Hz

L2

 

L3

 

E

 

L4

 

Separate Permanent Supply 230V / 1PH +N / 50Hz

N1

 

E

 

2

 

External Trace Heater Connections

N

 

230V/500W max.

502

 

(1) Evaporator Remote Pump Interlock 24VAC

522

 

502

 

Unit Remote On/Off 24VAC

505

 

502

 

Setback Setpoint Temperature switch

507

 

573

 

Circuit 1

Volt Free Common Alarm

574

 

Volt Free Alarm N/O

575

 

Volt Free Alarm N/C

576

 

Circuit 2

Volt Free Common Alarm

577

 

Volt Free Alarm N/O

578

 

Volt Free Alarm N/C

RX-/TX-

 

Network Connections

RX+/TX+

 

GND

 

CAUTION

(1) Must be directly wired to the chiller to validate warranty.

With Pumps

UCFC 75 - 450

L1

 

Mains incoming supply 400V / 3PH / 50Hz

L2

 

L3

 

E

 

L4

 


Separate Permanent Supply 230V / 1PH +N / 50Hz

N1

 

E

 

2

 

External Trace Heating Connections

N

 

230V/500W max

502

 

Pump/s Remote On/Off 24VAC

526

 

502

 

Unit Remote On/Off 24VAC

505

 

502

 

Setback Setpoint Temperature switch

507

 

573

 

Circuit 1

Volt Free Common Alarm

574

 

Volt Free Alarm N/O

575

 

Volt Free Alarm N/C

576

 

Circuit 2

Volt Free Common Alarm

577

 

Volt Free Alarm N/O

578

 

Volt Free Alarm N/C

RX-/TX-

 

Network Connections

RX+/TX+

 

GND

 