Chillers ultima compact freecool, Sound data, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 39: Global & directional sound level, Super quiet - dsq models

Advertising
background image

Chillers

ULTIMA COMPACT FREECOOL

Chillers

39

Technical Manual : 6259576 V1.2.0_02__2013

Sound Data

GLOBAL & DIRECTIONAL SOUND LEVEL

Super Quiet - DSQ Models

Sound Measurement

Overall

dB(A)

Frequency (Hz) dB

63

125

250

500

1000

2000

4000

UCFC75DSQ-2/1

Power

73

76

80

76

67

68

62

53

Pressure

@ 10m

41

44

48

44

35

36

30

21

UCFC100DSQ-3/1

Power

75

81

84

78

69

70

64

56

Pressure

@ 10m

43

49

52

46

37

38

32

24

UCFC125DSQ-4/1

Power

78

77

85

83

72

71

66

58

Pressure

@ 10m

46

45

53

51

40

39

34

26

UCFC150DSQ-4/1

Power

78

77

85

83

72

71

66

58

Pressure

@ 10m

46

45

53

51

40

39

34

26

UCFC160DSQ-8/2

Power

80

79

85

82

77

75

72

64

Pressure

@ 10m

48

47

53

50

45

43

40

32

UCFC180DSQ-8/2

Power

81

79

85

82

78

76

72

65

Pressure

@ 10m

49

47

53

50

46

44

40

33

UCFC200DSQ-8/2

Power

81

79

85

82

80

76

72

65

Pressure

@ 10m

49

47

53

50

48

44

40

33

UCFC225DSQ-10/2

Power

82

80

85

83

81

77

72

66

Pressure

@ 10m

50

48

53

51

49

45

40

34

UCFC250DSQ-10/2

Power

83

80

85

83

82

77

72

66

Pressure

@ 10m

51

48

53

51

50

45

40

34

UCFC275DSQ-12/2

Power

84

81

86

84

82

78

75

69

Pressure

@ 10m

52

49

54

52

50

46

43

37

UCFC300DSQ-12/2

Power

84

81

86

84

82

78

76

71

Pressure

@ 10m

52

49

54

52

50

46

44

39

UCFC330DSQ-16/2

Power

84

82

88

85

83

79

74

68

Pressure

@ 10m

51

49

55

52

50

46

41

35

UCFC360DSQ-16/2

Power

84

82

88

85

83

79

74

67

Pressure

@ 10m

51

49

55

52

50

46

41

34

UCFC400DSQ-16/2

Power

85

82

88

85

83

79

76

71

Pressure

@ 10m

52

49

55

52

50

46

43

38

UCFC450DSQ-16/2

Power

86

82

88

85

84

80

78

72

Pressure

@ 10m

53

49

55

52

51

47

45

39

1

dB(A) is the overall sound level, measured on the A scale.

2

All sound data measured at nominal conditions: Water in/out 12/7°C at 30°C ambient.

3

Figures based on standard unit, for units fitted with optional pump packages, please contact Airedale.

The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If the equipment is placed
adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for each side added.