Capacity data, Free cooling, Chillers ultima compact freecool – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 23: Performance data

Advertising
background image

Chillers

ULTIMA COMPACT FREECOOL

Chillers

23

Technical Manual : 6259576 V1.2.0_02__2013

Performance Data

CAPACITY DATA

– FREE COOLING

Where ΔT refers to the difference between Return Water and Ambient Temperatures eg:

T @ 12/7°C Water Temperature: 5°C Ambient = 7°C

Example: UCFC150DSQ-4/1, water @ 10/15, 30°C Ambient, DX mechanical cooling 144.9kW

(refer to

Capacity Data

– DX Mechanical Cooling

, on page 20).

UCFC125DSQ-4/1
UCFC150DSQ-4/1

Fre

e

Coo

li

n

g

(k

W)

25

50

75

100

125

3

4

5

6

7

8

9

10

11

16°C ΔT

6°C ΔT

8°C ΔT

10°C ΔT

12°C ΔT

14°C ΔT

Waterflow (l/s)

Flow =

144.9

= 7.43 l/s

5 x 3.9

Free Cooling Duty @ 5°C Ambient:

T = Return Water - Ambient

15°C

-

5°C

10°C

T

Free Cooling Duty = 79kW