Design Features & Information

MINIMUM SYSTEM WATER VOLUME CALCULATIONS

(DX Mechanical Cooling Mode Requirements)

GENERAL

Based on 20% Ethylene Glycol Concentration

METHOD 1 Where the system permanent heat load is known:

Vm =

Water Flow Rate (litres/minute) x Minimum Compressor Run Time (mins)
x Chiller Loading Factor

Where

Vm is the minimum water volume in litres
Minimum Compressor Run Time is 2 minutes


Chiller Loading Factor =

Minimum Turndown (kW) x 1.2

Permanent Heat Load

The Chiller Loading Factor limits:
Max

1.00

Min

0.25

Example 150 kW Chiller, 7/12°C Water, Model UCFC150D-3/1 with a permanent load of 60 kW

Vm =

150 x 60

x 2 x

40 x 1.2

= 738 Litres

3.9 x 5

60

METHOD 2 Where the system permanent heat load is unknown:

Vm =

Water Flow Rate (litres/hour) x Minimum Turndown Ratio x 1.2

Maximum Compressor Starts Per Hour

Where

Minimum Turndown Ratio = Minimum Stage Capacity (kW)

Chiller Full Capacity (kW)

Example 150 kW Chiller, 7/12°C Water, Model UCFC150D-3/1 permanent load unknown.

Vm =

150 x 3600

x

1

x 1.2

x

1

= 692 Litres

3.9 x 5

4

12

Method 1 is always preferred.