Universal Command #48 – Read Additional Device Status

Command #48 returns 8 bytes of data that is specific to the M2000 HART daughterboard The following table defines the

status information for the reply to this command Unused bits are not listed in the table and are always set to 0 Some of these

bits influence the device status bits shown in the Device Status Bits Set column:

Byte

Bit

Description

Class

Device Status Bits Set

0

0

Detector Error

Error

4, 7

1

Empty Pipe Error

Error

4, 7

2

Full Scale Flow Error

Warning

0, 4

3

Totalizer Rollover Error

Error

4, 7

4

Totalizer Rollover Status

Warning

4

5

Flow Simulation Status

Warning

4

6

Pulse Synchronization

Warning

Warning

4

7

ADC Interrupt Error

Error

4, 7

1

0

ADC Range Error

Error

4, 7

4

0

Internal Communication

Failure

Error

4, 7

1

Configuration Error

Warning

4

The “internal communication failure” status bit, byte 4 bit 0, is set when MODBUS communication between the meter and the

daughterboard have failed Verify that the diagnostic, bi-color LED on the daughterboard is blinking both status indicators

(red and green) If both colors are not observed, then power cycle the meter

The “Configuration Error” status bit, byte 4 bit 1, is set when a mismatch between the meter’s configuration and that reported

over the HART protocol Generally, this implies the intended value for the parameter was invalid Below are some examples for

how this bit could be set

Example #1: Intended value is invalid

If the configured function for output #1 is set to 24V DC supply, the output type has to be normally open If the intended

value for the output type is normally closed, the configuration error flag will be set indicating the intended value was invalid

due to its dependency on the function of the output

Example #2: Writing to a secured meter

If connected to a secured meter, and you try to change a parameter after the login timer has expired, the “Configuration Error”

indicates that the parameter image between HART and the M2000 is not equal