Fixed Current Mode (Multi-Drop)

The M2000 provides an active analog output This means it is the source of the analog signal When placing the meter into

fixed current mode, the M2000 shall fix the output current to 4 mA regardless of the primary variables value (that is, Flow

Rate) During this condition the device status bit 3 (PV Analog Channel Fixed) is set

To place the meter into fixed current mode, the polling address must be non-zero This is a HART specific parameter The

polling address is not accessible within the M2000 menu structure Changing this value when the meter is secured is not

prevented With reference to the HART DD, this parameter is located at Configuration > Hart > Hart Output > Poll Addr

Each meter to be commissioned for multi-drop should exercise the following procedure The default polling address for all

HART daughterboards is 0

1 Turn off power to all meters to be commissioned for HART multi-drop mode

IMPORTANT

As a result of the M2000 having an active analog output, only five M2000s can be configured for multi-drop mode within the

same network

2 Wire the meters in parallel as shown in Figure 5:

42

41

41

42

42

41

250 Ω

Load

Polling Address = 1

Polling Address = 2

Polling Address = 3

44

43

44

43

44

43

Amp Meter

12 mA

Figure 5: Wiring Meters in Parallel

3 Turn on power to one of the meters
4 Change the polling address to desired address As a suggestion, it may be desirable to change the installation data

while changing the polling address Installation data can provide additional means for identifying the meter on the

HART network

5 Repeat this procedure until all nodes on the HART multi-drop network are configured with a non-zero and unique

polling address

IMPORTANT

The analog output alarm mode has no effect while the meter is configured for multi-drop mode

Installation & Operation Manual