Follow these steps to install the daughterboard:

1 Prior to installing the daughterboard, verify or configure the M2000 Communication Port B Access the port settings

at Main Menu > Communications > Port B Settings

Parameter

Value

Comments

Port Address

001

Extended Port Address

Not applicable for HART

Baud Rate

38400

HART Daughterboard auto-bauds, all baud rates supported

Data Bits

8

Parity

EVEN

Stop Bits

1

2 Verify or configure the analog output range at 4…20 mA

Access the analog output range at Main Menu > Inputs/Outputs > Analog Output Range

3 Power off the M2000

DISCONNECT THE INPUT POWER BEFORE ACCESSING THE EQUIPMENT.

This step is important for the M2000 to properly recognize the HART daughterboard and fulfill HART compliance

4 Prior to inserting the daughterboard, install the foam insulation pad as shown below Be sure to align the groove with

the two screws attaching the detector or wall mount bracket to the enclosure The primary purpose of this pad is to

ensure the daughterboard is insulated from the enclosure wall It is important to install this pad flush with the top of

the enclosure wall

Figure 4: Installing Foam Insulation Pad

5 Insert the daughterboard into the 11-pin connector
6 Use the following information to make appropriate wiring of analog wires to the 4-pin customer connector

Pin Number

Pin Description

Comments

41

Analog Ground

42

Analog Signal

Requires minimum loop impedance of 230 Ω for communication

43

Analog Shield

Only for shielded wires

44

Chassis Jumper

Connect to screw in corner

7 Power on the M2000
8 Allow time for the daughterboard to properly power up and be recognized by the M2000 before navigating the

menus This time is typically 5 seconds If the HART daughterboard is not recognized, then the M2000 should be

power cycled

9 Verify recognition of the HART daughterboard Navigate to Main Menu > Info > Help The Daughterboard Info field

indicates the Daughterboard Type is HART

Apply insulation pad

flush with the top of

the housing

Installation & Operation Manual