Command Action Request

There are several remote actions that can be requested of the meter over HART Below is a table that defines the remote

actions that can be taken including the level of security required if the meter is secured

To issue an action to the meter, access the command action parameter at Configuration > M2000 > Advanced > Miscellaneous >

Service

Value

Security

Description

6

NONE

Save Totalizers to EEPROM

7

SERVICE

Clear T1 or T+

8

SERVICE

Clear T2 or T-

9

SERVICE

Clear T3 or Tn

10

SERVICE

Clear All Totalizers

11

SERVICE

Clear Port A Diagnostics

12

SERVICE

Clear Port B Diagnostics

13

SERVICE

Clear All Error Counts

21

SERVICE

Clear Power Off Totalizer

23

SERVICE

Remote Reset (power cycle)

27

SERVICE

Reset Batch Amount

28

NONE

Logoff Remote

No Action

Empty Pipe Calibration

Empty Pipe Calibration is an application embedded within the DD file that allows for remote calibration of empty pipe

Navigate to Configuration > M2000 > Advanced > Empty Pipe and select Empty Pipe Calib to start the application Follow the

on-screen instructions for further details

It may take up to 30 seconds for each pipe condition’s reading to stabilize During this time, the following message

displays, “Wait while reading stabilizes “

Executing the empty pipe calibration application will leave Empty Pipe enabled regardless of the state prior to

execution

M-Series® M2000 HART® Bi-Directional Communication Protocol Data Access